12
Publication No. 1637/ UPDATE
07
.1
9
Mat-No. 3003103
120 cm
l
≥
45 cm
r
≥
30 cm
r
≥
30 cm
1
2
1
2
Case 2
As is the case with case 1, no equipotential bonding connection element is required and thus the
HVI
light
Conductor
is not connected to the equipotential bonding system. A spacer with an insulating clearance of
41 cm (Part No. 106 852) is installed at a distance of 120 cm (measured from the connection element). The
adjustment area shown in Fig. 5b must be maintained.
The equivalent separation distance is „s“ ≤ 30 cm (in air).
- GRP spacer, Part No. 106 852
GRP length = 500 mm, plastic bushing,
plastic conductor holder (Ø 20 mm)
- Concrete base e.g. Part No. 102 075
- Base plate, Part No.102 060
- FB roof conductor holder, Part No. 253 015
-
Adapter (Ø 20 mm), Part No.
253 026
separation distance
s
≤
30 cm
No electrical, conductive or
earthed parts may be located in
this adjustment area, the
separation distance
"
s
"
has to
be
maintained!
HVI
light Conductor
insulating clear
ance =
41 cm
roof parapet
Fig. 5b
Case 2 without connection to the equipotential bonding system
(s
≤ 30 cm)