background image

C1000 Series Service & Maintenance Manual

Service and Repair

SECTION IV

Fig. L

Fig. M

Fig.K

After removing the wiring from the compressor motor, the motor may be removed by unscrewing the air discharge hose on the front left 
cylinder, and removing the four ½” nuts securing the head to the vibration isolation mounts. 

2.  Power Switches: The toggle switches located on the front center of the 
compressor control the individual compressor motors. If the pressure 
switch is operating correctly, remove the motor terminal cover on the back 
of the desired compressor motor. With the power switch in the on “up” 
position, check for voltage to the compressor motor as shown in Fig. K.  If 
the proper voltage is present, the power switch is good. If no voltage is 
present at the motor, replace the corresponding power switch. 

3.  Compressor Motor (head): The compressor motor turns the compressor crankshaft to generate air

fl

 ow to the system.   If the correct 

voltage is present on the L1 and L2 terminals as described in the testing procedure listed above, but the compressor hums and does not 
start, the start capacitor is defective. If the correct voltage is present but nothing happens, the head is defective.

To replace the motor, it is not required to cut the spade terminals from the wiring (see Figures L and M) for proper disassembly without 
cutting factory wiring. 

1.800.624.2793

13

Unpacking

Electrical

Summary of Contents for C1103

Page 1: ...D C1203 D C2106 D C2206 D C3210 C Series COMPRESSOR Copyright 2006 DCI All Rights Reserved D C1103 D C1203 D C2106 D C2206 D C3210 C Series COMPRESSOR Compressor Service Maintenance Manual 92311 Rev...

Page 2: ...1 www dcionline com www dcionline com...

Page 3: ...SERVICE REPAIR INSTRUCTIONS A Troubleshooting Chart B Electrical 1 Replacing Pressure Switch 2 Replacing Power Switch 3 Replacing Compressor Head 4 Replacing Time Operated Purge Valve C Pneumatic 1 Re...

Page 4: ...service procedures before attempting to service this machine Our unique dryer purge system operates much differently than conventional air compressors Understanding the proper operation and design wil...

Page 5: ...ons 1 Single 1 horsepower compressor head on 20 gal Horizontal tank See Fig A 2 Dual 1 horsepower compressor heads on 20 gal Horizontal tank See Fig B 3 Dual 1 horsepower heads on 30 gal horizontal ta...

Page 6: ...5 C1203 3 95 1 20 34 24 29 5 230 6 7 10 C2106 7 95 2 20 34 24 29 5 115 26 8 30 C2206 7 95 2 20 34 24 29 5 230 13 4 15 C3210 11 85 3 30 46 26 36 230 21 1 30 NOTE ALL VOLTAGES ARE 5 MODEL NUMBER MAXIMUM...

Page 7: ...ttom of the filter bowl The compressed air also travels through the coalescing filter element which removes 99 998 of all particles down to 0 01 microns A filter change indicator located on the top of...

Page 8: ...e compressor cycles off C The Left timer knob on the purge valve controls the duration of the purge cycles This timer is factory preset and should not be adjusted The factory setting is at the maximum...

Page 9: ...C1000 Series Service Maintenance Manual Theory of Oporation Theory of Operation THEORY OF OPERATION While Not Running Electrical Schematic SECTION II 1 800 624 2793 7...

Page 10: ...e element first turn off the compressor motor switches Then turn off the Dryer bypass valve as shown in Fig E With dryer bypass valve in OFF position press the TEST button on the time operated purge v...

Page 11: ...floor Check the filter screen inside the filter strainer valve as shown in Fig G If the strainer shutoff valve is on and the screen is not clogged replace the Time Operated Purge Valve with DCI part N...

Page 12: ...breaker Ensure that supply voltage matches equipment ratings Check for loose wiring Check contact points and adjust or replace Bleed pressure from system to ensure proper starting Ensure supply volta...

Page 13: ...or replace intake filter element Clean Replace valve plate Air leaks compressor too small to meet demand Add ventilation and or cooling to equipment room Clean or replace solenoid valve assembly Left...

Page 14: ...oltage indicated should agree with the machine data plate either 115 or 230 volt AC If no voltage is present check the circuit breaker Fig I Fig J ELECTRICAL If the proper voltage is present on the ou...

Page 15: ...on up position check for voltage to the compressor motor as shown in Fig K If the proper voltage is present the power switch is good If no voltage is present at the motor replace the corresponding po...

Page 16: ...embly 2 Turn OFF the strainer shutoff valve in Fig N 3 Remove the valve and replace with DCI Part Number 2011 for 230 volt machines OR DCI Part Number 2848 for 115 volt models 4 Return the strainer sh...

Page 17: ...Replace the differential filter indicator by unscrewing the entire assembly counterclockwise with a 15 16 6 point box end wrench Install the new indicator in the reverse order 3 Automatic Filter Float...

Page 18: ...er 2006 Coalescing Element 2135 Check Valve 2135 Check Valve 2014 Drying Chamber Assembly Pressure Gauge 2011 Automatic Purge Valve 230 Volt OR 2848 Automatic Puge Valve 115 Volt 2009 Strainer Shut Of...

Page 19: ...C1000 Series Service Maintenance Manual Illustrated Parts Breakdown SECTION V Unpacking Electrical Schematic 1 800 624 2793 17...

Page 20: ...ION V Unpacking Plumbing Schematic Left Motor Right Motor Check Valve Check Valve Aftercooling Tubing Coalescing Filter Condensate Drain Drying Chamber Flow Check Drying System Pressure Gauge Dryer By...

Page 21: ...1 800 624 2793 19...

Page 22: ...305 N Springbrook Road Newberg Oregon 97132 USA 503 538 8343 800 624 2793 www dcionline com...

Reviews: