Network separation device
DazeBox is not equipped with its own mains switch. The earth leakage
circuit breaker and/or the circuit breaker of the supply line act as a mains
separation device.
Power cable
The power cable must be a multi-core cable with a wire cross-section of 6
mm2.
Power cables must be dimensioned according to the following criteria:
▪
laying method;
▪
voltage drop;
▪
cable length;
▪
required power or current intensity;
We recommend using flexible cables to connect DazeBox, for ease of
wiring, especially with large cable cross-sections.
Parameter
Specification
Type of terminal block
Push-lock terminals
Wire cross-section per terminal block
(copper)
6 mm
2
Strip length
12 mm
Cable type
FG16OR16 or equivalent
Cable outer diameter for passage in
cable gland
from 13 to 18 mm
Some local regulations require shielded cables. The cable shielding must be
connected to the PE terminal at both ends of the cable.