2-10
Monitor output specifications
Output type
Source output (N channel MOSFET)
Rated output voltage
Power supply voltage
Minimum output voltage
Power supply voltage - 2.0V
Number of outputs
11 (Y4, Y5, Y6, Y7, Y10, Y11, Y12, Y13, Y14, Y15, Y16)
Point
20mA maximum
Maximum output current
total
220mA maximum
Leakage current
0.1mA maximum
Cable length
Note1
100m maximum (total wiring length per 1output)
Note1. For cables longer than 30m between SG-ONE and connected devices, use grounded
shielded cables to assure electromagnetic compatibility.
Monitor output equivalent circuit
Internal
circuit
Logic
circuit
Yn
V-
V+
The specifications of the monitor outputs changes depending on the Logic selected. See further
information in “Chapter 5 LOGIC”. The basic specifications are the same.
Warning
Do not use monitor outputs for safety related purposes. This may cause a loss of safety
functions in case of failure of the SG-ONE or peripherals.