2-11
Solenoid/Lamp output specifications
Output type
Source output (N channel MOSFET)
Rated output voltage
Power supply voltage
Minimum output voltage
Power supply voltage - 2.0V
Number of outputs
2
(
Y17, Y20
)
point
500mA maximum
Maximum output current
total
500mA maximum
Leakage current
0.1mA maximum
Allowable Inductive Load
Note1
L/R=25ms
Cable length
Note2
100m maximum (total wiring length per 1 output)
Note1. For protection of output circuits, protection devices such as diodes should be connected
to output circuits with inductive loads.
Note2. For cables longer than 30m between SG-ONE and connected devices, use grounded
shielded cables to assure electromagnetic compatibility.
Solenoid/lamp output equivalent circuit
Internal
circuit
Log ic
circuit
Y17,Y20
V -
V +
The specifications of the Solenoid/Lamp outputs changes depending on the Logic selected.
See further information in “Chapter 5 Logic”. But the basic specifications are the same.
Warning
Do not use solenoid/lamp outputs for safety related purposes. This may cause a loss of safety
functions in case of failure of the SG-ONE or peripherals.