6-2
5
ON OFF OFF Muting lamp error
(broken wire)
(For logic 4 only)
Broken wire of
muting lamp
wiring
Broken wire of
Muting lamp
Check functionality and
wiring of the muting
lamp.
Check the operation of
the muting lamp.
6
ON
ON
OFF Fault in power supply
or internal power
supply circuit
The voltage of
the power supply
to SG-ONE is
not within the
allowable range.
Check voltage of the
power supply to the
SG-ONE.
7
ON
ON
OFF Fault in power supply
or internal power
supply circuit
The voltage of
power supply to
SG-ONE is not
within the
allowable range.
Check voltage of power
supply to SG-ONE.
7
ON OFF OFF Internal
circuit
error
Internal failure of
the SG-ONE
Replace the SG-ONE.
9
ON
OFF OFF Noise filter error
Noise influences
to the SG-ONE
or input/output
line.
Check noise in the
surrounding
environment.
C
OFF ON OFF Changing to the
Configuration state
- -
The state of the input LEDs and monitoring output varies depending upon the logic selected.
Refer to “Chapter 4 BASIC OPERATIONS” and "Chapter 5 LOGIC" for details.