AMT58x-PB Profibus®
21
6.3 Modes of operation
Profibus-DP devices allow operation using different communication
modes (see Figure below):
NOTE
All parameters -except for
Preset value
- are transmitted in
Set_Prm
mode.
Preset value
is transmitted only in
Data_Exchange
mode.
Types of communication
Transmission of data between Master and Slave is carried out using
the following types of messages:
DDLM_Set_Prm:
Used for configuring the slave. This communication mode is
active immediately after power is turned ON and used to send
parameters from Master to Slave (see section “6.4
DDLM_Set_Prm“).
DDLM_Chk_Cfg:
Sets the number of bytes used for data transmission in
Data_Exchange
mode (see section “6.5 DDLM_Chk_Cfg“).
DDLM_Data_Exchange:
Used as "standard operation mode".
Used by Master to send the
Preset value
; used by Slave to
transmit position and velocity values (see section “6.6
DDLM_Data_Exchange“).
DDLM_Slave_Diag:
Used when power is turned on and whenever Master needs to
know diagnostic information from Slave device (see section “6.7
DDLM_Slave_Diag“).
Set_Slave_Address:
Used to set a new node number via BUS (service SAP55, see
section “6.8 Set_Slave_Address (service SAP55)“).
Power-ON
Wait_Prm
Wait_Cfg
Data_Exchang
Chk_Cfg_O
Set_Prm_O
Set_Prm_FAIL
Chk_Cfg_FAIL
Init_OK