AMT58x-PB Profibus®
10
4.5 Connection of the shield
Disentangle and shorten the shielding 1 and then bend it over the
part 2; finally place the ring nut 3 of the connector. Be sure that the
shielding 1 is in tight contact with the ring nut 3.
4.6 Node address: DIP A (Figure 1)
WARNING
Power supply must be turned off before performing this operation!
The node address must be set
via hardware using the DIP A
dip-switches located inside the
connection cap.
Allowed addresses are from 0 to
125. The default value is 1.
The node address must be
entered also in the software
interface, please refer to section “5.1.2 Adding a node to the project”
on page 16.
Turn the power supply off and set the node number in binary value:
consider that: ON=1, OFF=0
bit 1
LSB
2 3 4 5 6 7
MSB
8
not
used
2
0
2
1
2
2
2
3
2
4
2
5
2
6