5. MODES OF OPERATION
The genset will run if the front panel
RUN
button is pressed and will stop if the
STOP
button is
pressed. If requested a starting password may be assigned. The password is set using the program parameter
P_048
and has a value between 0 and 999. If the password is set to 0, the unit will directly run the genset
when the
RUN
button is pressed. If the password is set to a value other than 0, the unit will ask the password
when the
RUN
button is pressed. In this case the upper and midrange display will show : “PAS”, “S=?”. Enter
the password value to the lower display using (
▲
) and (
▼
) buttons then press
MENU
button. If the password
is correct, the engine will run.
If the Remote Start program parameter (
P_042
) is set to 1, the genset may also be run via a signal
applied to the
SPARE-2 (22)
input. In this situation both the
Remote Start Input
and front panel
RUN
and
STOP
buttons are enabled. For example if a
Remote Start
signal arrives when the engine is stopped, then
the engine will run. It may be stopped either by pressing the
STOP
button or by removing the
Remote Start
signal.
The load transfer should be made externally by manual command.
6. OTHER FEATURES
6.1 Remote Start Operation
The unit offers the possibility of
REMOTE START
mode of operation.
If the program parameter
P_042
is set to
1
then the unit will enter to the Remote Start operation. In
this mode, the engine will run and stop with the Remote Start signal.
It is also necessary to set the program parameter
P_119
to
3
in order to prevent the alarms generated
from this input.
Even if an operation password is set, it will not be asked with a Remote Start signal.
The Remote Start signal should be connected to the
SPARE_2
(
22
) input. It may be a NO or NC
contact, switching to either battery positive or battery negative. These selections are made using programming
menu.
6.2 Sender type Selection
The unit has the ability to adapt to any type of oil pressure and temperature senders. The
commonly used standard sender characteristics are recorded in memory and selectable from a list.
However non standard senders may also be used by entering their characteristics to the table.
Oil Pressure Sender Type Selection:
The oil pressure sender is selected using parameter P_019. The selectable sender types are:
0:
The sender characteristics are defined in table using parameters P_131 to P_142.
1:
VDO 0-7 bars (10-180 ohms)
2:
VDO 0-10 bars (280-20 ohms)
3:
DATCON 0-7 bars (240-33 ohms)
4:
DATCON 0-10 bars (240-33 ohms)
5:
DATCON 0-7 bars (0-90 ohms)
6:
DATCON 0-10 bars (0-90 ohms)
7:
DATCON 0-7 bars (75-10 ohms)
Temperature Sender Selection:
The temperature sender is selected using parameter P_020. The selectable sender types are:
0:
The sender characteristics are defined in table using parameters P_143 to P_154.
1:
VDO
2:
DATCON DAH type
3:
DATCON DAL type