5. MODES OF OPERATION 

 
 

The  genset  will  run  if  the  front  panel 

RUN

  button  is  pressed  and  will  stop  if  the 

STOP

  button  is 

pressed. If requested a starting password may be assigned. The password is set using the program parameter 

P_048 

and has a value between 0  and 999. If the password is set to 0, the unit will directly run the genset 

when the 

RUN

 button is pressed. If the password is set to a value other than 0, the unit will ask the password 

when the 

RUN

 button is pressed. In this case the upper and midrange display will show : “PAS”, “S=?”. Enter 

the password value to the lower display using (

) and (

) buttons then press 

MENU

 button. If the password 

is correct, the engine will run. 
 

If the Remote Start program parameter (

P_042

) is set to 1, the genset may also be run via a signal 

applied to the 

SPARE-2 (22) 

input. In this situation both the 

Remote Start Input

 and front panel 

RUN

 and 

STOP

 buttons are enabled. For example if a 

Remote Start

 signal arrives when the engine is stopped, then 

the engine will run. It may be stopped either by pressing the 

STOP

 button or by removing the 

Remote Start

 

signal.

 

 

The load transfer should be made externally by manual command. 

 

6. OTHER FEATURES 

 

6.1 Remote Start Operation 

 

 

The unit offers the possibility of 

REMOTE START

 mode of operation.  

 

If the program parameter 

P_042

 is set to 

1

 then the unit will enter to the Remote Start operation. In 

this mode, the engine will run and stop with the Remote Start signal.  

 

It is also necessary to set the program parameter 

P_119

 to 

3

 in order to prevent the alarms generated 

from this input. 

 

Even if an operation password is set, it will not be asked with a Remote Start signal. 

 

The Remote Start signal should be connected to the 

SPARE_2

 (

22

) input. It may be a NO or NC 

contact, switching to either battery positive or battery negative. These selections are made using programming 
menu. 

6.2 Sender type Selection 

 

 

The unit has the ability to adapt to any type of oil pressure and temperature senders. The 

commonly used standard sender characteristics are recorded in memory and selectable from a list. 
However non standard senders may also be used by entering their characteristics to the table. 
 

Oil Pressure Sender Type Selection: 

The oil pressure sender is selected using parameter P_019. The selectable sender types are: 

0:

 The sender characteristics are defined in table using parameters P_131 to P_142. 

1: 

VDO 0-7 bars (10-180 ohms) 

2:

 VDO 0-10 bars (280-20 ohms) 

3:

 DATCON 0-7 bars (240-33 ohms) 

4:

 DATCON 0-10 bars (240-33 ohms)  

5:

 DATCON 0-7 bars (0-90 ohms) 

6:

 DATCON 0-10 bars (0-90 ohms) 

7:

 DATCON 0-7 bars (75-10 ohms) 

 

Temperature Sender Selection: 

The temperature sender is selected using parameter P_020. The selectable sender types are: 

0:

 The sender characteristics are defined in table using parameters P_143 to P_154. 

1: 

VDO 

2:

 DATCON DAH type 

3:

 DATCON DAL type

 

Summary of Contents for DKG-317

Page 1: ...wer measurement Genset power factor measurement Periodic maintenance request indicator Engine hours counter Event logging Statistical counters Field adjustable parameters RS 232 serial port Free MS Wi...

Page 2: ...s 3 2 Digital Display 4 ALARMS AND WARNINGS 5 MODES OF OPERATION 6 OTHER FEATURES 6 1 Remote start operation 6 2 Sender type selection 6 3 Service Request Display 6 4 Engine Hour Meter 6 5 Modem conne...

Page 3: ...the retaining steel spring and connectors from the unit then pass the unit through the mounting opening The unit will be maintained in its position by the steel spring Engine body must be grounded fo...

Page 4: ...porate appropriate short circuit backup protection e g a fuse or circuit breaker of High Breaking Capacity HBC at least 1500A 6 Use cables of adequate current carrying capacity at least 0 75mm 2 and t...

Page 5: ...table from a list 19 START RELAY Output 10A 28VDC This relay controls the engine cranking 20 FUEL RELAY Output 10A 28VDC This relay is used for fuel solenoid control It is internally connected to term...

Page 6: ...hours or time duration after previous service has elapsed ALARM GROUP Red If a fault condition resulting to the engine shutdown has occurred the related alarm led turns on steadily If a warning condi...

Page 7: ...generator phase to neutral voltages UV VW WU generator phase to phase voltages If the service counters group is displayed then this display will show the counter name In programming mode it displays P...

Page 8: ...med HIGH TEMPERATURE Set if a signal is detected at the High Temperature Switch input or the coolant temperature value measured from the sender is above the programmed limit Warning P_017 and alarm P_...

Page 9: ...ter P_042 is set to 1 then the unit will enter to the Remote Start operation In this mode the engine will run and stop with the Remote Start signal It is also necessary to set the program parameter P_...

Page 10: ...ing engine hours and the remaining time limit are kept stored in a non volatile memory and are not modified by power supply failures The remaining time and engine hours to service may be checked via t...

Page 11: ...0 CASECOM USB TO SERIAL CONVERTER MODEL RS 01 7 EVENT LOGGING The unit keeps records of the last 12 events in order to supply information for the service personal The events are stored in a circular m...

Page 12: ...er failures To exit the program mode press one of the mode selection keys If no button is pressed during 1 minute the program mode will be cancelled automatically Pgm Definition Unit Std Val Descripti...

Page 13: ...High Battery Voltage Alarm V 33 0 If the battery voltage goes over this limit this will generate a BATTERY alarm and the engine will stop 15 Low Oil Pressure Warning Bar 1 5 If the oil pressure measu...

Page 14: ...limits P_008 P_011 and SPEED FAULT alarm occurs 25 Not used 26 Preheat timer sec 1 This is the time after the fuel solenoid is energized and before the genset is started During this period the PREHEA...

Page 15: ...ngine Hours hours 200 The SERVICE REQUEST led indicator will turn on after this quantity of engine hours from the last service If the period is set to 0 no SERVICE REQUEST will be generated depending...

Page 16: ...n 22 74 RELAY 10 function 23 75 RELAY 11 function 24 76 RELAY 12 function 25 77 RELAY 13 function 26 78 RELAY 14 function 27 79 RELAY 15 function 28 80 RELAY 16 function 29 81 RELAY 17 function 30 82...

Page 17: ...e 1 Battery positive 88 Response delay 0 0 No delay 1 Delayed 4sec HIGH TEMPERATURE SWITCH INPUT Pgm Description Std 89 Operation 0 0 Alarm the engine stops and horn relay operates 2 Warning the horn...

Page 18: ...relay operates 2 Warning the horn relay operates 3 No operation 108 Fault monitoring 0 0 Always 1 After holdoff timer 2 When mains present 109 Latching 0 0 Non latching 1 Latching 110 Contact type 0 0...

Page 19: ...t type 0 0 Normally open 1 Normally closed 129 Switching 0 0 Battery negative 1 Battery positive 130 Response delay 0 0 No delay 1 Delayed 4sec Parameters from P_131 to P_142 define the ohm bar charac...

Page 20: ...red as 0 An example table is given below The sensor characteristics used in this table are 38 C 342 ohms 82 C 71 ohms 104 C 40 ohms 121 C 30 ohms Pgm Description Unit Value 143 Point_1 resistor ohm 30...

Page 21: ...the Amp readings are correct Current transformers are not connected to the correct inputs or some of the CTs are connected with reverse polarity Determine the correct connections of each individual C...

Page 22: ...between BATTERY and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So the starting will also be removed when the D pulls...

Page 23: ...Internally connected to battery positive via 4700 ohm resistor Analog inputs Resistor input 0 to 5000 ohms connected to the battery negative Sources 10 mA when closed to battery negative Measurement...

Page 24: ...DKG 317 User Manual V 01 19 01 10 2009 24 14 CONNECTION DIAGRAM...