DKG-317 User Manual                                                                         V-01.19 

(01.10.2009)

 

 

 

 

 

 

- 16 -   

 
 

The parameters from P_065 to P_082 define the functions of relay outputs. The unit has 4 relay 

outputs and 2 of them have programmable functions. The fixed function relays are Fuel and Start.  
 

The relays may be extended up to 20 using 

Relay Extension Modules

. RELAY-1 and RELAY-2 

with programmable functions are inside the unit. Other relays are in the optional Extension Modules. 
 

The function of a programmable relay output may be selected from the below list.  

 
 

   RELAY FUNCT

İ

ON LIST

 

Pgm 

Description 

Std 

65 

RELAY-1 function 

01 

66 

RELAY-2 function 

03 

67 

RELAY-3 function 

16 

68 

RELAY-4 function 

17 

69 

RELAY-5 function 

18 

70 

RELAY-6 function 

19 

71 

RELAY-7 function 

20 

72 

RELAY-8 function 

21 

73 

RELAY-9 function 

22 

74 

RELAY-10 function 

23 

75 

RELAY-11 function 

24 

76 

RELAY-12 function 

25 

77 

RELAY-13 function 

26 

78 

RELAY-14 function 

27 

79 

RELAY-15 function 

28 

80 

RELAY-16 function 

29 

81 

RELAY-17 function 

30 

82 

RELAY-18 function 

31 

 

00 

Fuel 

01 

Horn 

02 

Start 

03 

Stop 

04 

05 

06 

Choke 

07 

Preheat 

08 

Alarm 

09 

Warning 

10 

Alarm+Warning 

11 

Automatic ready 

12 

13 

14 

15 

Genset ready 

16 

Oil switch alarm 

17 

Temp switch alarm 

18 

Level switch alarm 

19 

Rectifier alarm 

20 

Emerg.Stop alarm 

21 

Spare-1 Alarm 

22 

Spare-2 Alarm 

23 

 

24 

Oil sender alarm 

25 

Temp sender alarm 

26 

Speed alarm 

27 

Start fail alarm 

28 

Charge alarm 

29 

Overload alarm 

30 

Voltage alarm 

31 

Battery High alarm 

32 

Oil switch warning 

33 

Temp switch warn. 

34 

Level switch warn. 

35 

Rectifier warning 

36 

Emerg Stop warn. 

37 

Spare-1 warning 

38 

Spare-2 warning 

39 

40 

Oil sender warning 

41 

Temp sender warn. 

42 

Speed warning 

43 

Stop Fail warning 

44 

Charge warning 

45 

Battery low warning 

46 

47 

Battery high warn. 

 

 

Summary of Contents for DKG-317

Page 1: ...wer measurement Genset power factor measurement Periodic maintenance request indicator Engine hours counter Event logging Statistical counters Field adjustable parameters RS 232 serial port Free MS Wi...

Page 2: ...s 3 2 Digital Display 4 ALARMS AND WARNINGS 5 MODES OF OPERATION 6 OTHER FEATURES 6 1 Remote start operation 6 2 Sender type selection 6 3 Service Request Display 6 4 Engine Hour Meter 6 5 Modem conne...

Page 3: ...the retaining steel spring and connectors from the unit then pass the unit through the mounting opening The unit will be maintained in its position by the steel spring Engine body must be grounded fo...

Page 4: ...porate appropriate short circuit backup protection e g a fuse or circuit breaker of High Breaking Capacity HBC at least 1500A 6 Use cables of adequate current carrying capacity at least 0 75mm 2 and t...

Page 5: ...table from a list 19 START RELAY Output 10A 28VDC This relay controls the engine cranking 20 FUEL RELAY Output 10A 28VDC This relay is used for fuel solenoid control It is internally connected to term...

Page 6: ...hours or time duration after previous service has elapsed ALARM GROUP Red If a fault condition resulting to the engine shutdown has occurred the related alarm led turns on steadily If a warning condi...

Page 7: ...generator phase to neutral voltages UV VW WU generator phase to phase voltages If the service counters group is displayed then this display will show the counter name In programming mode it displays P...

Page 8: ...med HIGH TEMPERATURE Set if a signal is detected at the High Temperature Switch input or the coolant temperature value measured from the sender is above the programmed limit Warning P_017 and alarm P_...

Page 9: ...ter P_042 is set to 1 then the unit will enter to the Remote Start operation In this mode the engine will run and stop with the Remote Start signal It is also necessary to set the program parameter P_...

Page 10: ...ing engine hours and the remaining time limit are kept stored in a non volatile memory and are not modified by power supply failures The remaining time and engine hours to service may be checked via t...

Page 11: ...0 CASECOM USB TO SERIAL CONVERTER MODEL RS 01 7 EVENT LOGGING The unit keeps records of the last 12 events in order to supply information for the service personal The events are stored in a circular m...

Page 12: ...er failures To exit the program mode press one of the mode selection keys If no button is pressed during 1 minute the program mode will be cancelled automatically Pgm Definition Unit Std Val Descripti...

Page 13: ...High Battery Voltage Alarm V 33 0 If the battery voltage goes over this limit this will generate a BATTERY alarm and the engine will stop 15 Low Oil Pressure Warning Bar 1 5 If the oil pressure measu...

Page 14: ...limits P_008 P_011 and SPEED FAULT alarm occurs 25 Not used 26 Preheat timer sec 1 This is the time after the fuel solenoid is energized and before the genset is started During this period the PREHEA...

Page 15: ...ngine Hours hours 200 The SERVICE REQUEST led indicator will turn on after this quantity of engine hours from the last service If the period is set to 0 no SERVICE REQUEST will be generated depending...

Page 16: ...n 22 74 RELAY 10 function 23 75 RELAY 11 function 24 76 RELAY 12 function 25 77 RELAY 13 function 26 78 RELAY 14 function 27 79 RELAY 15 function 28 80 RELAY 16 function 29 81 RELAY 17 function 30 82...

Page 17: ...e 1 Battery positive 88 Response delay 0 0 No delay 1 Delayed 4sec HIGH TEMPERATURE SWITCH INPUT Pgm Description Std 89 Operation 0 0 Alarm the engine stops and horn relay operates 2 Warning the horn...

Page 18: ...relay operates 2 Warning the horn relay operates 3 No operation 108 Fault monitoring 0 0 Always 1 After holdoff timer 2 When mains present 109 Latching 0 0 Non latching 1 Latching 110 Contact type 0 0...

Page 19: ...t type 0 0 Normally open 1 Normally closed 129 Switching 0 0 Battery negative 1 Battery positive 130 Response delay 0 0 No delay 1 Delayed 4sec Parameters from P_131 to P_142 define the ohm bar charac...

Page 20: ...red as 0 An example table is given below The sensor characteristics used in this table are 38 C 342 ohms 82 C 71 ohms 104 C 40 ohms 121 C 30 ohms Pgm Description Unit Value 143 Point_1 resistor ohm 30...

Page 21: ...the Amp readings are correct Current transformers are not connected to the correct inputs or some of the CTs are connected with reverse polarity Determine the correct connections of each individual C...

Page 22: ...between BATTERY and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So the starting will also be removed when the D pulls...

Page 23: ...Internally connected to battery positive via 4700 ohm resistor Analog inputs Resistor input 0 to 5000 ohms connected to the battery negative Sources 10 mA when closed to battery negative Measurement...