1.3 Wiring the Unit 

 

 

WARNING: THE UNIT IS NOT FUSED. 

Use external fuses for 

Generator phase: U-V-W  

Battery positive: BAT(+). 

Install the fuses as nearly as possible to                 

the unit in a place easily accessible for the user. 

The fuse rating should be 6 Amps.

 

 
 

 

WARNING: ELECTRICITY CAN KILL 

 ALWAYS disconnect the power BEFORE connecting the unit.

 

 
 

 

1)  ALWAYS remove the plug connectors when inserting wires with a screwdriver.  
2)  ALWAYS refer to the National Wiring Regulations when conducting installation. 
3)  An appropriate and readily accessible set of disconnection devices (e.g. 

automatic fuses) MUST be provided as part of the installation. 

4)  The disconnection device must NOT be fitted in a flexible cord. 
5)  The building mains supply MUST incorporate appropriate short-circuit backup 

protection (e.g. a fuse or circuit breaker) of High Breaking Capacity (HBC, at 
least 1500A). 

6)  Use cables of adequate current carrying capacity (at least 0.75mm

2

) and 

temperature range. 

 

 

2. INPUTS AND OUTPUTS 

 
RS-232 SERIAL PORT:

 This connector provides serial data input and output for various purposes like remote 

monitoring and remote programming. 

 
EXTENSION CONNECTOR: 

This connector is intended for the connection to output extension modules. The 

optional relay extension module provides 8 programmable 16A relay outputs. The unit allows the use of up to 2 
I/O extension modules. 
 

Term  Function 

Technical data 

Description 

 

No connection to this terminal. 

Generator phase 
inputs, 0-300V-AC

 

Connect the generator phases to these inputs. 
The  generator  phase  voltages  upper  and 
lower limits are programmable.

 

GENERATOR NEUTRAL 

Input, 0-300V-AC

 

Neutral terminal for the generator phases.

 

*

 

 

No connection to these terminals.

 

*

 

*

 

*

 

10 

*

 

 
 

Summary of Contents for DKG-317

Page 1: ...wer measurement Genset power factor measurement Periodic maintenance request indicator Engine hours counter Event logging Statistical counters Field adjustable parameters RS 232 serial port Free MS Wi...

Page 2: ...s 3 2 Digital Display 4 ALARMS AND WARNINGS 5 MODES OF OPERATION 6 OTHER FEATURES 6 1 Remote start operation 6 2 Sender type selection 6 3 Service Request Display 6 4 Engine Hour Meter 6 5 Modem conne...

Page 3: ...the retaining steel spring and connectors from the unit then pass the unit through the mounting opening The unit will be maintained in its position by the steel spring Engine body must be grounded fo...

Page 4: ...porate appropriate short circuit backup protection e g a fuse or circuit breaker of High Breaking Capacity HBC at least 1500A 6 Use cables of adequate current carrying capacity at least 0 75mm 2 and t...

Page 5: ...table from a list 19 START RELAY Output 10A 28VDC This relay controls the engine cranking 20 FUEL RELAY Output 10A 28VDC This relay is used for fuel solenoid control It is internally connected to term...

Page 6: ...hours or time duration after previous service has elapsed ALARM GROUP Red If a fault condition resulting to the engine shutdown has occurred the related alarm led turns on steadily If a warning condi...

Page 7: ...generator phase to neutral voltages UV VW WU generator phase to phase voltages If the service counters group is displayed then this display will show the counter name In programming mode it displays P...

Page 8: ...med HIGH TEMPERATURE Set if a signal is detected at the High Temperature Switch input or the coolant temperature value measured from the sender is above the programmed limit Warning P_017 and alarm P_...

Page 9: ...ter P_042 is set to 1 then the unit will enter to the Remote Start operation In this mode the engine will run and stop with the Remote Start signal It is also necessary to set the program parameter P_...

Page 10: ...ing engine hours and the remaining time limit are kept stored in a non volatile memory and are not modified by power supply failures The remaining time and engine hours to service may be checked via t...

Page 11: ...0 CASECOM USB TO SERIAL CONVERTER MODEL RS 01 7 EVENT LOGGING The unit keeps records of the last 12 events in order to supply information for the service personal The events are stored in a circular m...

Page 12: ...er failures To exit the program mode press one of the mode selection keys If no button is pressed during 1 minute the program mode will be cancelled automatically Pgm Definition Unit Std Val Descripti...

Page 13: ...High Battery Voltage Alarm V 33 0 If the battery voltage goes over this limit this will generate a BATTERY alarm and the engine will stop 15 Low Oil Pressure Warning Bar 1 5 If the oil pressure measu...

Page 14: ...limits P_008 P_011 and SPEED FAULT alarm occurs 25 Not used 26 Preheat timer sec 1 This is the time after the fuel solenoid is energized and before the genset is started During this period the PREHEA...

Page 15: ...ngine Hours hours 200 The SERVICE REQUEST led indicator will turn on after this quantity of engine hours from the last service If the period is set to 0 no SERVICE REQUEST will be generated depending...

Page 16: ...n 22 74 RELAY 10 function 23 75 RELAY 11 function 24 76 RELAY 12 function 25 77 RELAY 13 function 26 78 RELAY 14 function 27 79 RELAY 15 function 28 80 RELAY 16 function 29 81 RELAY 17 function 30 82...

Page 17: ...e 1 Battery positive 88 Response delay 0 0 No delay 1 Delayed 4sec HIGH TEMPERATURE SWITCH INPUT Pgm Description Std 89 Operation 0 0 Alarm the engine stops and horn relay operates 2 Warning the horn...

Page 18: ...relay operates 2 Warning the horn relay operates 3 No operation 108 Fault monitoring 0 0 Always 1 After holdoff timer 2 When mains present 109 Latching 0 0 Non latching 1 Latching 110 Contact type 0 0...

Page 19: ...t type 0 0 Normally open 1 Normally closed 129 Switching 0 0 Battery negative 1 Battery positive 130 Response delay 0 0 No delay 1 Delayed 4sec Parameters from P_131 to P_142 define the ohm bar charac...

Page 20: ...red as 0 An example table is given below The sensor characteristics used in this table are 38 C 342 ohms 82 C 71 ohms 104 C 40 ohms 121 C 30 ohms Pgm Description Unit Value 143 Point_1 resistor ohm 30...

Page 21: ...the Amp readings are correct Current transformers are not connected to the correct inputs or some of the CTs are connected with reverse polarity Determine the correct connections of each individual C...

Page 22: ...between BATTERY and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So the starting will also be removed when the D pulls...

Page 23: ...Internally connected to battery positive via 4700 ohm resistor Analog inputs Resistor input 0 to 5000 ohms connected to the battery negative Sources 10 mA when closed to battery negative Measurement...

Page 24: ...DKG 317 User Manual V 01 19 01 10 2009 24 14 CONNECTION DIAGRAM...

Reviews: