Parameters from P_083 to P_130 program the functions of the digital inputs. The programmable
properties of digital inputs are:
-action to be taken upon arrival of the fault signal (alarm, warning,etc...),
-when the fault monitoring will be enabled,
-latching of the fault signal,
-contact type (NO/NC)
-switching (bat+, bat-)
-response delay
LOW OIL PRESSURE SWITCH INPUT
Pgm Description
Std
83
Operation
0
0:
Alarm (the engine stops and horn relay operates))
2:
Warning (the horn relay operates)
3:
No operation
84
Fault monitoring
1
0:
Always
1:
After holdoff timer
2:
When mains present
85
Latching
1
0:
Non latching
1:
Latching
86
Contact type
0
0:
Normally open
1:
Normally closed
87
Switching
0
0:
Battery negative
1:
Battery positive
88
Response delay
0
0:
No delay
1:
Delayed (4sec)
HIGH TEMPERATURE SWITCH INPUT
Pgm Description
Std
89
Operation
0
0:
Alarm (the engine stops and horn relay operates))
2
Warning (the horn relay operates)
3
No operation
90
Fault monitoring
0
0:
Always
1:
After holdoff timer
2:
When mains present
91
Latching
1
0:
Non latching
1:
Latching
92
Contact type
0
0:
Normally open
1:
Normally closed
93
Switching
0
0:
Battery negative
1:
Battery positive
94
Response delay
0
0:
No delay
1:
Delayed (4sec)
COOLANT LEVEL SWITCH INPUT
Pgm Description
Std
95
Operation
0
0:
Alarm (the engine stops and horn relay operates))
2:
Warning (the horn relay operates)
3:
No operation
96
Fault monitoring
0
0:
Always
1:
After holdoff timer
2:
When mains present
97
Latching
0
0:
Non latching
1:
Latching
98
Contact type
0
0:
Normally open
1:
Normally closed
99
Switching
0
0:
Battery negative
1:
Battery positive
100
Response delay
1
0:
No delay
1:
Delayed (4sec)