DKG-317 User Manual V-01.19
(01.10.2009)
- 14 -
Pgm Definition
Unit
Std Val
Description
20
Temperature sender type
-
1
This parameter selects the temperature sender
type:
0:
The sender characteristics are defined in
table using parameters P_143 to P_154.
1:
VDO
2:
DATCON DAH type
3:
DATCON DAL type
21
Hysteresis Voltage
V
8
This parameter provides the mains and genset
voltage limits with a hysteresis feature in order
to prevent faulty decisions.
For example, when the mains are present, the
mains voltage low limit will be used as the
programmed low limit
P_004
. When the mains
fail, the low limit will be used as
P_004+P_021
.
It is advised to set this value to 8 volts.
22
Not used
23
Holdoff timer
sec
8
This parameter defines delay after the engine
runs and before the fault monitoring is enabled.
24
Overcurrent / Excess
Power / Frequency Timer
sec
3
This is the period between the current or active
power goes over the limits
(P_002/P_003)
and
OVERLOAD
alarms occurs.
This is also the period between the frequency
goes out of the limits (
P_008/P_011)
and
SPEED
FAULT
alarm occurs.
25
Not used
26
Preheat timer
sec
1
This is the time after the fuel solenoid is
energized and before the genset is started.
During this period the
PREHEAT
relay output is
energized (if defined by programming)
27
Start Timer
sec
6
This is the maximum start period. Starting will
be automatically cancelled if the genset fires
before the timer.
28
Wait between Starts
sec
10
This is the waiting period between two start
attempts.
29
Engine Heating Timer
sec
3
This is the period after the engine runs and
before the Genset Ready signal is issued.
30
Not used
31
Cooling Timer
min
1.0
This is the period that the generator runs for
cooling purpose after the load is transferred to
mains.
32
Not used
33
Not used
34
Stop Timer
sec
10
This is the maximum time duration for the
engine to stop. During this period the STOP
relay output is energized (if defined by
programming). If the genset has not stopped
after this period, a
STOP FAIL
alarm will occur.
35
Start Attempts
-
3
This is the maximum number of start attempts.
36
Horn Timer
sec
10
This is the period during which the
HORN
relay
is active. If the period is set to 0, this will mean
that the period is unlimited.
37
Not used