DKG-317 User Manual                                                                         V-01.19 

(01.10.2009)

 

 

 

 

 

 

- 14 -   

 

Pgm  Definition 

Unit 

Std Val 

Description 

20 

Temperature sender type 

This parameter selects the temperature sender 
type: 

0:

 The sender characteristics are defined in 

table using parameters P_143 to P_154. 

1: 

VDO 

2:

 DATCON DAH type 

3:

 DATCON DAL type

 

 

21 

Hysteresis Voltage 

This parameter provides the mains and genset 
voltage limits with a hysteresis feature in order 
to prevent faulty decisions. 
For example, when the mains are present, the 
mains voltage low limit will be used as the 
programmed low limit 

P_004

. When the mains 

fail, the low limit will be used as 

P_004+P_021

It is advised to set this value to 8 volts. 

22 

Not used 

 

 

 

23 

Holdoff timer 

sec 

This parameter defines delay after the engine 
runs and before the fault monitoring is enabled. 

24 

Overcurrent / Excess 
Power / Frequency Timer 

sec 

This is the period between the current or active 
power goes over the limits 

(P_002/P_003)

 and 

OVERLOAD

 alarms occurs.  

This is also the period between the frequency 
goes out of the limits (

P_008/P_011) 

and 

SPEED 

FAULT 

alarm occurs. 

25 

Not used 

 

 

 

26 

Preheat timer 

sec 

This is the time after the fuel solenoid is 
energized and before the genset is started. 
During this period the 

PREHEAT

 relay output is 

energized (if defined by programming) 

27 

Start Timer 

sec 

This is the maximum start period. Starting will 
be automatically cancelled if the genset fires 
before the timer. 

28 

Wait between Starts 

sec 

10 

This is the waiting period between two start 
attempts. 

29 

Engine Heating Timer 

sec 

This is the period after the engine runs and 
before the Genset Ready signal is issued. 

30 

Not used 

 

 

 

31 

Cooling Timer 

min 

1.0 

This is the period that the generator runs for 
cooling purpose after the load is transferred to 
mains. 

32 

Not used 

 

 

 

33 

Not used 

 

 

 

34 

Stop Timer 

sec 

10 

This is the maximum time duration for the 
engine to stop. During this period the STOP 
relay output is energized (if defined by 
programming). If the genset has not stopped 
after this period, a 

STOP FAIL

 alarm will occur. 

35 

Start Attempts 

This is the maximum number of start attempts. 

36 

Horn Timer 

sec 

10 

This is the period during which the 

HORN

 relay 

is active. If the period is set to 0, this will mean 
that the period is unlimited. 

37 

Not used 

 

 

 

 

Summary of Contents for DKG-317

Page 1: ...wer measurement Genset power factor measurement Periodic maintenance request indicator Engine hours counter Event logging Statistical counters Field adjustable parameters RS 232 serial port Free MS Wi...

Page 2: ...s 3 2 Digital Display 4 ALARMS AND WARNINGS 5 MODES OF OPERATION 6 OTHER FEATURES 6 1 Remote start operation 6 2 Sender type selection 6 3 Service Request Display 6 4 Engine Hour Meter 6 5 Modem conne...

Page 3: ...the retaining steel spring and connectors from the unit then pass the unit through the mounting opening The unit will be maintained in its position by the steel spring Engine body must be grounded fo...

Page 4: ...porate appropriate short circuit backup protection e g a fuse or circuit breaker of High Breaking Capacity HBC at least 1500A 6 Use cables of adequate current carrying capacity at least 0 75mm 2 and t...

Page 5: ...table from a list 19 START RELAY Output 10A 28VDC This relay controls the engine cranking 20 FUEL RELAY Output 10A 28VDC This relay is used for fuel solenoid control It is internally connected to term...

Page 6: ...hours or time duration after previous service has elapsed ALARM GROUP Red If a fault condition resulting to the engine shutdown has occurred the related alarm led turns on steadily If a warning condi...

Page 7: ...generator phase to neutral voltages UV VW WU generator phase to phase voltages If the service counters group is displayed then this display will show the counter name In programming mode it displays P...

Page 8: ...med HIGH TEMPERATURE Set if a signal is detected at the High Temperature Switch input or the coolant temperature value measured from the sender is above the programmed limit Warning P_017 and alarm P_...

Page 9: ...ter P_042 is set to 1 then the unit will enter to the Remote Start operation In this mode the engine will run and stop with the Remote Start signal It is also necessary to set the program parameter P_...

Page 10: ...ing engine hours and the remaining time limit are kept stored in a non volatile memory and are not modified by power supply failures The remaining time and engine hours to service may be checked via t...

Page 11: ...0 CASECOM USB TO SERIAL CONVERTER MODEL RS 01 7 EVENT LOGGING The unit keeps records of the last 12 events in order to supply information for the service personal The events are stored in a circular m...

Page 12: ...er failures To exit the program mode press one of the mode selection keys If no button is pressed during 1 minute the program mode will be cancelled automatically Pgm Definition Unit Std Val Descripti...

Page 13: ...High Battery Voltage Alarm V 33 0 If the battery voltage goes over this limit this will generate a BATTERY alarm and the engine will stop 15 Low Oil Pressure Warning Bar 1 5 If the oil pressure measu...

Page 14: ...limits P_008 P_011 and SPEED FAULT alarm occurs 25 Not used 26 Preheat timer sec 1 This is the time after the fuel solenoid is energized and before the genset is started During this period the PREHEA...

Page 15: ...ngine Hours hours 200 The SERVICE REQUEST led indicator will turn on after this quantity of engine hours from the last service If the period is set to 0 no SERVICE REQUEST will be generated depending...

Page 16: ...n 22 74 RELAY 10 function 23 75 RELAY 11 function 24 76 RELAY 12 function 25 77 RELAY 13 function 26 78 RELAY 14 function 27 79 RELAY 15 function 28 80 RELAY 16 function 29 81 RELAY 17 function 30 82...

Page 17: ...e 1 Battery positive 88 Response delay 0 0 No delay 1 Delayed 4sec HIGH TEMPERATURE SWITCH INPUT Pgm Description Std 89 Operation 0 0 Alarm the engine stops and horn relay operates 2 Warning the horn...

Page 18: ...relay operates 2 Warning the horn relay operates 3 No operation 108 Fault monitoring 0 0 Always 1 After holdoff timer 2 When mains present 109 Latching 0 0 Non latching 1 Latching 110 Contact type 0 0...

Page 19: ...t type 0 0 Normally open 1 Normally closed 129 Switching 0 0 Battery negative 1 Battery positive 130 Response delay 0 0 No delay 1 Delayed 4sec Parameters from P_131 to P_142 define the ohm bar charac...

Page 20: ...red as 0 An example table is given below The sensor characteristics used in this table are 38 C 342 ohms 82 C 71 ohms 104 C 40 ohms 121 C 30 ohms Pgm Description Unit Value 143 Point_1 resistor ohm 30...

Page 21: ...the Amp readings are correct Current transformers are not connected to the correct inputs or some of the CTs are connected with reverse polarity Determine the correct connections of each individual C...

Page 22: ...between BATTERY and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So the starting will also be removed when the D pulls...

Page 23: ...Internally connected to battery positive via 4700 ohm resistor Analog inputs Resistor input 0 to 5000 ohms connected to the battery negative Sources 10 mA when closed to battery negative Measurement...

Page 24: ...DKG 317 User Manual V 01 19 01 10 2009 24 14 CONNECTION DIAGRAM...

Reviews: