Before installation:
Read the user manual carefully, determine the correct connection diagram.
Remove all connectors and mounting brackets from the unit, then pass the unit
through the mounting opening.
Put mounting brackets and tighten. Do not tighten too much, this can brake the
enclosure.Self mating brackets do not require tightening.
Make electrical connections with plugs removed from sockets, then place plugs to
their sockets.
Make sure that relay outputs are not overloaded. If necessary use extra contactors.
Below conditions may damage the device:
Incorrect connections.
Incorrect power supply voltage.
Voltage at measuring terminals beyond specified range.
Current at measuring terminals beyond specified range.
Overload or short circuit at relay outputs
Below conditions may cause abnormal operation:
Power supply voltage below minimum acceptable level.
Power supply frequency out of specified limits
Current transformers not matching related phases.
Current transformer polarity incorrect. (if automatic correction is not applied).
Inadequate on-delay setting
Inadequate off-delay setting.
Current Transformers must be used for current
measurement.
No direct connection allowed.
1. INSTALLATION