DKG-108 User Manual V-1.0
(10.08.2011)
-19-
DISPLAY
DESCRIPTION
MIN
STD MAX
STEPPING PROGRAM SELECTION
This parameter selects
between
LEGACY
and
OPTIMAL
stepping programs.
The unit is advised to be operated under
OPTIMAL
program.
Program details are emphasized in
chapter 5.
1
10
10
STEP TURN-ON DELAY
When a new capacitor combination is
required, the unit continues
measurements during this timer and the
new combination found at the end of this
timer is directed to step outputs.
1 sec
20 sec 2000
sec
STEP TURN-OFF DELAY
When a new capacitor combination is
set to step outputs, stepping is disabled
during this period.
1 sec
30 sec 2000
sec
DISCHARGE TIMER
Common discharge timer for all steps. A
deactivated bank cannot be reactivated
before this timer has expired.
3 sec
60 sec 2000
sec
CAPACITOR TYPE (CON1...CON8)
Selects capacitor connection type.
If
“
Prog
” parameter is selected between
1
and
8
, these parameters have no
effect and all banks are supposed to be
3 phased.
0
3 phase capacitor
1
single phase capacitor at phase L1
2
single phase capacitor at phase L2
3
single phase capacitor at phase L3
0
0
3