DKG-108 User Manual V-1.0
(10.08.2011)
-29-
DISPLAY
DESCRIPTION
MIN
STD MAX
THD(V) HIGH ALARM LIMIT
Any phase voltage THD above this limit
will generate a high THD(V) alarm.
If this limit is set to zero then the alarm is
not monitored.
0 %
0 %
99%
THD(V) ALARM DELAY
For a high THD(V) alarm, the limit must
be overridden during this period.
0 sec
30 sec 200
sec
THD(V) ALARM FUNCTION
0
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
1
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
2
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
0
0
3