DKG-108 User Manual V-1.0
(10.08.2011)
-28-
DISPLAY
DESCRIPTION
MIN
STD MAX
OVERCURRENT ALARM LIMIT
Any phase current above this limit will
generate an overcurrent alarm.
If this limit is set to zero then the alarm is
not monitored.
0 A
0 A
5000 A
OVERCURRENT ALARM DELAY
For an overcurrent alarm, the limit must
be overridden during this period.
0 sec
30 sec 200
sec
OVERCURRENT ALARM FUNCTION
0
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
1
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
2
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
0
0
3