DKG-108 User Manual V-1.0
(10.08.2011)
-31-
DISPLAY
DESCRIPTION
MIN
STD MAX
CAPACITOR VALUE LOSS ALARM
LIMIT
If the measured capacitor bank rating is
less than the percent defined by this
parameter, compared to its nominal
value, then a capacitor value loss alarm
is given.
The low capacitor value must be
measured at least 3 times below the
limit.
If this limit is set to zero then the alarm is
not monitored.
0 %
0 %
80 %
CAPACITOR VALUE LOSS ALARM
DELAY
For a value loss alarm, the limit must be
overridden during this period.
0 sec
30 sec 200
sec
CAPACITOR VALUE LOSS ALARM
FUNCTION
0
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
1
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“
MutE
”.
2
In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3
In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
0
0
3