DKG-108 User Manual V-1.0
(10.08.2011)
-18-
DISPLAY
DESCRIPTION
MIN
STD MAX
PASSWORD ENTRY
The user password is required. The
password is determined by the program
parameter
“
PASS
”. The factory set value
is
“
1
”.
The password
“
3282
” is always valid.
0
1
9999
AUTOMATIC SETUP
When this parameter is set to
1
, and if
the unit is in
MANUAL
mode, steps are
activated consecutively and bank ratings
are measured.
0
0
1
RESETTING DYNAMIC STEP VALUES
AND FAULT COUNTERS
When this parameter is set to
1
, fault
counters and dynamic bank values are
reset.
0
0
1
RESETTING STEP COUNTERS
When this parameter is set to
1
, step
activation and operation counters are
reset.
0
0
1
RETURN TO FACTORY SETTINGS
When this parameter is set to
1
, all
program parameters return back to
factory set values.
0
0
1
TARGETcos
ø
This is the target
cos
ø
value that the unit
is trying to reach in
AUTO
mode. The
value can be adjusted between 0.800
capacitive and 0.800 inductive.
Capacitive values are shown in c.999
format. Inductive values are shown in
0.999 format.
0.800
cap.
0.999
ind.
0.800
ind.
ADJUSTING THE NUMBER OF STEPS
The number of used steps can be
adjusted between 1 and 8. Unused steps
are not taken into account in the
stepping program.
1
8
8
7.4 PROGRAM PARAMETER LIST