46
MENU
- To
Group 6 - NETWORK
SELECT
- To view Group 6 sub-menus
Display will read:
6-1 UNIT & NETWORK ID
SELECT
or
- To view current setting
Display will read:
6-1 UNIT & NETWORK ID
UNIT & NETWORK ID: nnn
SELECT
or
- To change current setting
Units may given a numerical ID from 001 to 260. Units cannot share the same ID. Units
will not respond to a network unless a separate ID is entered for each unit.
Factory setting is:
UNIT & NETWORK ID: 001
MENU
- To view next sub-menu
Display will read:
6-2 NETWORK PROTOCOL
SELECT
or
- To view current setting
Display will read:
6-2 NETWORK PROTOCOL
aaaaaaaaaaaaaaaaaaaa
Data Aire offers protocols to interface with a number of building management systems
(BMS). Units must be provided with optional communication cards.
The following choices are available:
BACNET IP
BACNET MS/TP MASTER
BACKNET MS/TP SALVE
LONWORKS
JOHNSON
CONTROLS
MODBUS
TCP
MODBUS RTU
MODBUS ASCII
METASYS N2
SNMPv1/v2c
Factory setting is based on protocol ordered. The appropriate protocol will be factory set.
MENU
- To view next sub-menu
Display will read:
6-3 IP ADDRESS
SELECT
or
- To view current setting
Display will read:
6-3 IP ADDRESS
IP ADDRESS OCTET 1:
0.
0. 0. 0
SELECT
or
- To change current setting -
This applies to all OCTET settings
MENU
- To view OCTET 2
Display will read:
6-3 IP ADDRESS
IP ADDRESS OCTET 2:
0.
0
. 0. 0
Group 6
Menus 6-2 to 6-15 are locked.
To modify you have to unlock
the DAP III.
If protocol is changed the DAP
III panel needs to be reset.
Turn panel OFF then ON.