34
MENU
- Press MENU
button to view next sub-menu
Display will read:
4-7 LOW DISCHARGE TEMP ALARM LIMIT
SELECT
or
- Press SELECT button to view current setting
Display will read:
4-7 LOW DISCHARGE TEMP ALARM LIMIT
SET AT: nnF
(C)
NOTE:
Low discharge temperature alarm limit requires an optional discharge air sensor.
Sensor is factory installed if ordered with unit. If sensor is not installed, the following
message will be displayed:
SENSOR NOT INSTALLED ON THIS UNIT
If sensor is installed the temperature alarm limit has a range of 45 to 60ºF (7.2
to 15.6ºC). Low discharge temperature alarm can also be disabled through Sub-
Menu 4-7. If disabled, the following message will displayed:
DISABLE LOW DISCHARGE TEMP ALARM
SELECT
or
- To change current setting
Factory setting is: 52º F (C)
MENU
- To view next sub-menu
Display will read:
4-8 COMPRESSOR SHORT-CYCLE ALARM
SELECT
or
- To view current setting
Display will read:
4-8 COMPRESSOR SHORT-CYCLE ALARM
COMPRESSOR SHORT-CYCLE ALARM: ON
SELECT
or
- To change current setting
NOTE:
There are two settings available ON or OFF. A compressor short-cycle alarm will
activate if the compressor has been energized ten (10) times in a one (1) hour period.
Compressor life can be shortened by allowing frequent cycling. On-going short-cycle
alarm problems should be analyzed before selecting “OFF.”
Factory setting is: ON
MENU
- To view next sub-menu
Display will read:
4-9 WATER UNDER FLOOR ALARM ACTION
SELECT
or
- To view current setting
Display will read:
4-9 WATER UNDER FLOOR ALARM ACTION
ACTION: aaaa
There are three available selections:
NONE
- Audio alarm only.