32
MENU
- To proceed to Group 4 - ALARMS
Display will read:
GROUP 4 – ALARMS
SELECT
- To view Group 4 - ALARMS
Display will read:
4-1 AUDIO ALARM MODE
SELECT
or
- To display current setting
Display will read:
4-1 AUDIO ALARM MODE
AUDIO ALARM: LONG BEEP
SELECT
or
- to scroll through the available selections.
The following can be viewed, audio alarm will also sound:
NONE
SHORT
BEEP
LONG
BEEP
FULL
ON
Factory setting is: LONG BEEP
MENU
- To view next sub-menu
Display will read:
4-2 CHANGE HI TEMPERATURE ALARM LIMIT
SELECT
or
- To view current setting
Display will read:
4-2 CHANGE HI TEMPERATURE ALARM LIMIT
SET AT: xxF
(C)
SELECT
or
- To change current setting
(High temperature alarm can be adjusted from 70 to 90ºF (21 to 32ºC) in
1
º increments. There is also a disable
function. When the disable function is set the display will read
:
4-2 CHANGE HI TEMPERATURE ALARM LIMIT
DISABLE HI TEMPERATURE ALARM
Factory setting is: 80F (C)
MENU
- To view next sub-menu
Display will read:
4-3 CHANGE LO TEMPERATURE ALARM LIMIT
SELECT
or
- To view current setting
Display will read:
4-3 CHANGE LO TEMPERATURE ALARM LIMIT
SET AT: xxF
(C)
SELECT
or
- To change current setting
Low temperature alarm can be adjusted from 55 to 75ºF (12.8 to 23.9ºC) in 1º increments. There is also a
disable function
.
When the disable function is set the display will read
:
Group 4