39
Factory setting is:
LOCAL ALARM 4: SEE TAG INSIDE DOOR
MENU
- To view next sub-menu
Display will read:
4-19 DELAY FOR OPT. ALARM INPUT 4
SELECT
or
- To view current setting
Display will read:
4-19 DELAY FOR OPT. ALARM INPUT 4
ALARM DELAY: nnn SECONDS
SELECT
or
- To change current setting
Alarm delay can be set from 1 to 900 seconds in one second increments. The delay can also be
set to OFF. When set to OFF, the display will read:
4-19 DELAY FOR OPT. ALARM INPUT 4
ALARM DELAY: OFF
Factory setting is:
5 SECONDS
MENU
- To view next sub-menu
Display will read:
4-20 REMOTE ALARM 1 SELECTION
SELECT
or
- To view current setting
Display will read:
4-20 REMOTE ALARM 1 SELECTION
aaaaaaaaa
Remote alarms may be grouped. To add or remove alarms press the SILENCE button. The added alarm will
be designated by an asterisk (*). Only those alarms with the asterisk (*) will be included in REMOTE ALARM 1.
SELECT
or
- To scroll though available alarms.
Available alarms for group 1:
CHECK HUMIDIFIER CYLINDER
LOCAL ALARM 3
CHILLED WATER SENSOR PROBLEM ALARM
LOCAL ALARM 4
COMPRESSOR SHORT-CYCLE
LOW DISCHARGE AIR TEMPERATURE ALARM
CUSTOM MESSAGE ALARM, OPT INPUT 1
LOW HUMIDITY ALARM
CUSTOM MESSAGE ALARM, OPT INPUT 2
LOW PRESSURE COMPRESSOR 1 ALARM
CUSTOM MESSAGE ALARM, OPT INPUT 3
LOW PRESSURE COMPRESSOR 2 ALARM
CUSTOM MESSAGE ALARM, OPT INPUT 4
LOW TEMPERATURE ALARM
DIRTY FILTER ALARM
LOW VOLTAGE ALARM
DISCHARGE AIR SENSOR PROBLEM ALARM
MAINTENANCE REQUIRED ALARM
FAN MOTOR OVERLOAD ALARM
MANUAL OVERRIDE ALARM
FIRE STAT ALARM
NO AIR FLOW ALARM
HIGH CONDENSATE WATER LEVEL
NO WATER FLOW ALARM
HIGH HUMIDITY ALARM
POWER PROBLEM, RESTART ALARM
HIGH PRESSURE/INTERNAL OVERLOAD: COMP 1 REHEAT & HUMIDIFICATION INHIBITED
HIGH PRESSURE/INTERNAL OVERLOAD: COMP 2 REHEAT INHIBITED
HIGH TEMPERATURE ALARM
SMOKE DETECTOR ALARM
HUMIDIFICATION INHIBITED
STANDBY PUMP ON ALARM
HUMIDIFIER PROBLEM ALARM
TEMPERATURE SENSOR PROBLEM ALARM
HUMIDITY SENSOR PROBLEM ALARM
UNIT IN STANDBY, ALL FUNCTIONS ARE OFF
LOCAL ALARM 1
UPS/ALTERNATE POWER ON ALARM
LOCAL ALARM 2
WATER DETECTION PROBE ALARM