VLT 5000 series
FC 302 series
Parameter 314 Terminal 60,
Analogue Input
current
3-17 Reference Resource 3
7-00 Speed PID Feedback Source
1-93 Thermistor Resource
4-20 Torque Limit Factor Source
Options
[0] No Operation Par. 3-17 Reference resource 3 set
to [0] No function
[1] Reference
Par. 3-17 Reference resource 3 set
to [2] Analog input 54 Par. 7-00
Speed PID
Feedback Source set to [7]
Analog input 54
[2] Feedback
signal
Par. 7-00 Speed PID Feedback
Source set to [7] Analog input 54
[3] Torque limit
Par. 3-17 Reference resource 3 set
to [2] Analog input 54 Par. 4-20
Torque Limit
Factor Source set to [6] Analog in
54
[4] Relative
reference
Not supported
Comments The HW switch S202 for analogue input 54 must be
set to current (ON).
Table 5.101 Conversion of Parameter 314
VLT 5000 series
FC 302 series
Parameter 315 Terminal 60, min.
scaling
6-22 Terminal 54 Low
Current
Range
0.0 – 20.0 mA
0.00 – Par. 6-23
Table 5.102 Conversion of Parameter 315
VLT 5000 series
FC 302 series
Parameter 316 Terminal 60, max.
scaling
6-23 Teminal 54 High
Current
Range
0.0 – 20.0 mA
Par. 6-22 - 20.00 mA
Table 5.103 Conversion of Parameter 316
VLT 5000 series
FC 302 series
Parameter
317 Time Out
6-00 Live Zero Timeout Time
Range
0 – 99 sec
0 – 99 sec
Table 5.104 Conversion of Parameter 317
VLT 5000 series
FC 302 series
Parameter 318 Function after time
out
6-01 Live Zero Timeout
Function
Options
[0] Off
[0] Off
[1] Freeze output
frequency
[1] Freeze output
frequency
[2] Stop
[2] Stop
[3] Jogging
[3] Jog
[4] Max Speed, p202
[4] Max Speed
[5] Stop and trip
[5] Stop and trip
Table 5.105 Conversion of Parameter 318
VLT 5000 series
FC 302 series
Parameter 319 Terminal 42,
Output
Digital = Par. 5-32 DO X30/7
(MCB 101)
Analogue values = Par. 6-50 AO
42
Pulse = Par. 5-66 DO X30/6
Parameter 321 Terminal 45,
Output
Digital = Par. 5-33 DO X30/7
(MCB 101)
Analogue values= Par. 6-60 AO
X30/8
Pulse = Par. 5-66 DO X30/6
Options
[0] No function
Par. 5-32 = [0] No operation
[1] Control Ready
Par. 5-32 = [1] Control Ready
[2] Ready signal
Par. 5-32 = [2] Drive ready
[3] Ready - Remote
Control
Par. 5-32 = [3] Drive rdy/rem
ctrl
[4] Enabled, no
warning
Par. 5-32 = [4] Enable / no
warning
[5] Running
Par. 5-32 = [5] VLT
®
running
[6] Running, no
Warning
Par. 5-32 = [6] Running /no
warning
[7] Running within
range, no Warning
Par. 5-32 = [7] Run in range/no
warning
[8] Run at
reference, no
Warning
Par. 5-32 = [8] Run on ref/no
warning
[9] Alarm
Par. 5-32 = [9] Alarm
[10] Alarm or
Warning
Par. 5-32 = [10] Alarm or
Warning
[11] Torque limit
Par. 5-32 = [11] At torque limit
[12] Out of current
range
Par. 5-32 = [12] Out of current
range
[13] Above I low
Par. 5-32 = [13] Below current,
low
1)
[14] Under I high
Par. 5-32 = [14] Above current,
high
1)
Table 5.106 Conversion of Parameters 319 to 321
Parameter Mapping Lists
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
24
MG34N202 - Rev. 2013-10-15
5