VLT 5000 series
FC 302 series
Parameter 101 Torque charac-
teristic
1-03 Torque Characteristics
1-04 Overload Mode
14-40 VT Level
Options
[7] High variable
torque with
medium starting
torque
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 66%
Par. 1-04 Over load = [0] High
[8] High variable
torque with high
starting torque
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 85%
Par. 1-04 Over load = [0] High
[11] Normal
constant torque
Par. 1-03 = [0] Constant torque
Par. 1-04 Over load = [1] Normal
[12] Normal
variable torque low
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 45%
Par. 1-04 Over load = [1] Normal
[13] Normal
variable torque
medium
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 66%
Par. 1-04 Over load = [1] Normal
[14] Normal
variable torque
high
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 85%
Par. 1-04 Over load = [1] Normal
[15] Normal special
motor characteristic
Par. 1-01 = [0] U/f
Par. 1-04 Over load = [1] Normal
[16] Normal
variable torque
with low constant
starting torque
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 45%
Par. 1-04 Over load = [1] Normal
[17] Normal
variable torque
with medium
constant starting
torque
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 66%
Par. 1-04 Over load = [1] Normal
[18] Normal
variable torque
with high constant
starting torque
Par. 1-03 = [1] Variable torque
Par. 14-40 VT level = 85%
Par. 1-04 Over load = [1] Normal
Table 5.21 Conversion of Parameter 101
VLT 5000 series
FC 302 series
Parameter
102 Motor Power
1-20 Motor Power [kW]
Range
0.18 – 600 kW
0.09 – 3000 kW
Table 5.22 Conversion of Parameter 102
VLT 5000 series
FC 302 series
Parameter
103 Motor Voltage
1-22 Motor Voltage
Range
200 – 600 Volt
50 – 1000 V
Table 5.23 Conversion of Parameter 103
VLT 5000 series
FC 302 series
Parameter
104 Motor frequency
1-23 Motor Frequency
Range
20 -1000 Hz
20 -1000 Hz
Table 5.24 Conversion of Parameter 104
VLT 5000 series
FC 302 series
Parameter 105 Motor Current
1-24 Motor Current
Range
Power Unit dependable
Power Unit dependable
Table 5.25 Conversion of Parameter 105
VLT 5000 series
FC 302 series
Parameter 106 Rated motor speed 1-25 Motor Nominal Speed
Range
100 – 60000
10 – 60000
Table 5.26 Conversion of Parameter 106
VLT 5000 series
FC 302 series
Parameter 107 Automatic motor
adaptation
1-29 Automatic Motor
Adaptation (AMA)
Options
[0] Adaptation off
[0] Off
[1] Adaptation on, Rs
and Xs
[1] Enable complete AMA
[2] Adaptation on, RS
[2] Enable reduce AMA
Table 5.27 Conversion of Parameter 107
VLT 5000 series
FC 302 series
Parameter 108 Stator resistor
1-30 Stator Resistance (Rs)
Range
Power Unit dependable 0.0140 – 140.0000
Table 5.28 Conversion of Parameter 108
VLT 5000 series
FC 302 series
Parameter 109 Stator reactance
1-35 Main Reactance (Xh)
Range
Power Unit dependable 1.0000 – 10000.0000
Table 5.29 Conversion of Parameter 109
VLT 5000 series
FC 302 series
Parameter 110 Motor magnetizing at
0 RPM
1-50 Motor Magneti-
sation at Zero Speed
Range
0 – 300%
0 – 300%
Table 5.30 Conversion of Parameter 110
VLT 5000 series
FC 302 series
Parameter
111 Min. frequency
normal magnetizing
1-52 Min Speed
Normal Magnetising
[Hz]
Range
0.1 – 10.0 Hz
0.3 – 10.0 Hz
Table 5.31 Conversion of Parameter 111
VLT 5000 series
FC 302 series
Parameter 113 Load compensation at
low speed
1-60 Low Speed Load
Compensation
Range
0 – 300%
0 – 300%
Table 5.32 Conversion of Parameter 113
Parameter Mapping Lists
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
MG34N202 - Rev. 2013-10-15
15