VLT 5000 series
FC 302 series
Parameter 305 Terminal 29, input
5-13 Terminal 29 Digital
Input
Options
[0] No function
[0] No operation
[1] Reset
[1] Reset
[2] Stop inverse
[6] Stop inverse
[3] Only start clockwise,
on
[12] Enable start forward
[4] Only start
anticlockwise, on
[13] Enable start reverse
[5] Jog
[14] Jog
[6] Preset reference, on
[15] Preset reference, on
[7] Preset reference, lsb
[16] Preset reference bit 0
[8] Preset reference, msb
[17] Preset reference bit 1
[9] Freeze reference
[19] Freeze reference
[10] Freeze output
[20] Freeze output
[11] Speed up
[21] Speed up
[12] Speed down
[22] Speed down
[13] Choice of Setup, lsb
[23] Setup select bit 0
[14] Choice of Setup, msb [24] Setup select bit 1
[15] Catch up
[28] Catch up
[16] Slow down
[29] Slow down
[17] Ramp 2
[34] Ramp bit 0
[18] Mains failure inverted Not supported
[28] Pulse reference
[32] Pulse input
[29] Data change lock
Not supported
Table 5.92 Conversion of Parameter 305
VLT 5000 series
FC 302 series
Parameter 306 Terminal 32, input
5-14 Terminal 32 Digital
Input
Options
[0] No function
[0] No operation
[1] Reset
[1] Reset
[2] Stop inverse
[6] Stop inverse
[3] Only start clockwise,
on
[12] Enable start forward
[4] Jog
[14] Jog
[5] Preset reference, on
[15] Preset reference, on
[6] Preset reference, lsb
[16] Preset reference bit 0
[7] Freeze reference
[19] Freeze reference
[8] Freeze output
[20] Freeze output
[9] Speed up
[21] Speed up
[10] Choice of Setup, lsb [23] Setup select bit 0
[11] Choice of Setup,
msb / Speed up
Not supported
[12] Catch up
[28] Catch up
[13] Ramp 2
[34] Ramp bit 0
[14] Mains failure
inverted
Not supported
[24] Encoder input 2A
[0] No operation
[29] Data change lock
Not supported
Table 5.93 Conversion of Parameter 306
VLT 5000 series
FC 302 series
Parameter 307 Terminal 33, input
5-15 Terminal 33 Digital
Input
7-00 Speed PID Feedback
Source
Options
[0] No function
[0] No operation
[1] Reset
[1] Reset
[2] Stop inverse
[6] Stop inverse
[3] Only start
anticlockwise, on
[13] Enable start reverse
[4] Jog
[14] Jog
[5] Preset reference, on
[15] Preset reference, on
[6] Preset reference, msb [17] Preset reference bit 1
[7] Freeze reference
[19] Freeze reference
[8] Freeze output
[20] Freeze output
[9] Speed down
[22] Speed down
[10] Choice of Setup,
msb
[24] Setup select bit 1
[11] Choice of Setup,
msb / Speed down
Not supported
[12] Slow down
[29] Slow down
[13] Ramp 2
[34] Ramp bit 0
[14] Mains failure
inverted
Not supported
[24] Pulse feedback
[32] Pulse input,
Parameter 700 = [9]
Frequency input 33
[25] Encoder input 2B
[0] No operation
Parameter 700 = [1] 24 V
encoder
[29] Data change lock
Not supported
Table 5.94 Conversion of Parameter 307
Parameter Mapping Lists
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
22
MG34N202 - Rev. 2013-10-15
5