ALARM 247, Power card temperature
This alarm is only for F frame adjustable frequency drives. It is equivalent to Alarm 69. The report
value in the alarm log indicates which power module generated the alarm:
1 = left most inverter module.
2 = middle inverter module in F2 or F4 drive.
2 = right inverter module in F1 or F3 drive.
3 = right inverter module in F2 or F4 drive.
5 = rectifier module.
ALARM 248, Illegal power section configuration
This alarm is only for F frame adjustable frequency drives. It is equivalent to Alarm 79. The report
value in the alarm log indicates which power module generated the alarm:
1 = left most inverter module.
2 = middle inverter module in F2 or F4 drive.
2 = right inverter module in F1 or F3 drive.
3 = right inverter module in F2 or F4 drive.
5 = rectifier module.
ALARM 250, New spare part
The power or switch mode power supply has been exchanged. The adjustable frequency drive
type code must be restored in the EEPROM. Select the correct type code in par. 14-23
Typecode
Setting
according to the label on the unit. Remember to select ‘Save to EEPROM’ to complete.
ALARM 251, New type code
The adjustable frequency drive has a new type code.
4 Troubleshooting
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
4-20
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
4