1.9 Ratings Tables
DC Voltage Levels
380–480 and 380–500 units
525–690 units
Inrush Circuit Enabled
370 VDC
548 VDC
Inrush Circuit Disabled
395 VDC
600 VDC
Inverter Undervoltage Disable
402 VDC
553 VDC
Undervoltage Warning
423 VDC
585 VDC
Inverter Undervoltage Re-Enable (warning re-
set)
442 VDC
602 VDC
Overvoltage Warning (without brake)
817 VDC
1084 VDC
Dynamic Brake Turn On
810 VDC
1099 VDC
Inverter Overvoltage Re-Enable (warning re-
set)
821 VDC
1099 VDC
Overvoltage Warning (with brake)
828 VDC
1109 VDC
Overvoltage Trip
855 VDC
1130 VDC
Line power supply 3 x 380–480/500 V
Model number
FC102/202
P110 P132 P160 P200 P250
FC302
P90K P110 P132 P160 P200
Normal overload current ratings (110%):
Output current
Nominal [A] (380–440 V)
212
260
315
395
480
MAX (60 sec) [A] (380–440 V)
233
286
347
434
528
Nominal [A] (441–500 V)
190
240
302
361
443
MAX (60 sec) [A] (441–500 V)
209
264
332
397
487
Output
Nominal [kVA] (400 V)
147
180
218
274
333
Nominal [kVA] (460 V)
151
191
241
288
353
Nominal [kVA] (500 V)
165
208
262
313
384
Typical shaft output
[kW] (400 V)
110
132
160
200
250
[HP] (460 V)
150
200
250
300
350
[kW] (500 V)
132
160
200
250
315
High overload torque (160%):
Output current
Nominal [A] (380–440 V)
177
212
260
315
395
MAX (60 sec) [A] (380–440 V)
266
318
390
473
593
Nominal [A] (441–500 V)
160
190
240
302
361
MAX (60 sec) [A] (441–500 V)
240
285
360
453
542
Output
Nominal [kVA] (400 V)
123
147
180
218
274
Nominal [kVA] (460 V)
127
151
191
241
288
Nominal [kVA] (500 V)
139
165
208
262
313
Typical shaft output
[kW] (400 V)
90
110
132
160
200
[HP] (460 V)
125
150
200
250
300
[kW] (500 V)
110
132
160
200
250
Power loss Normal overload [W]
3234 3782 4213 5117 5893
Power loss High overload [W]
2641 2995 3425 3910 4625
Limits and Ranges
Overcurrent Warning
VLT A
RMS
Out
329
394
484
586
735
Overcurrent Alarm (1.5 sec delay)
VLT A
RMS
Out
329
394
484
586
735
Ground Fault Alarm
VLT A
RMS
Out
80
95
120
151
180
Short Circuit Alarm
VLT A
RMS
Out
420
502
616
747
936
Heatsink Overtemperature
Degrees C
85
90
105
105
115
Heatsink Undertemperature Warning
Degrees C
0
0
0
0
0
Power Card Ambient Overtemperature Degrees C
60
60
60
60
60
Power Card Ambient Undertemperature Degrees C
-20
-20
-20
-20
-20
Line Phase Warning (5 sec delay)
DC Bus Ripple VAC
50
50
50
50
50
Line Phase Alarm (25 sec delay)
DC Bus Ripple VAC
50
50
50
50
50
1 Introduction
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
1-8
MG.90.L1.22 - VLT
®