[Hand On]
Enables control of the adjustable frequency drive via the LCP. [Hand On] also starts the motor,
and it is now possible to enter the motor speed data by means of the arrow keys. The key can be
selected as
Enable
[1] or
Disable
[0] via par. 0-40
[Hand on] Key on LCP
.
The following control signals will still be active when [Hand On] is activated:
•
[Hand On] - [Off] - [Auto On]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
NOTE!
External stop signals activated by means of control signals or a serial bus will over-
ride a
start
command via the LCP.
[Off]
stops the connected motor. The key can be selected as Enable [1] or Disable [0] via
par. 0-41
[Off] Key on LCP
. If no external stop function is selected and the [Off] key is inactive,
the motor can only be stopped by disconnecting the line power supply.
[Auto On]
enables the adjustable frequency drive to be controlled via the control terminals and/or serial
communication. When a start signal is applied on the control terminals and/or the bus, the ad-
justable frequency drive will start. The key can be selected as Enable [1] or Disable [0] via
par. 0-42
[Auto on] Key on LCP
.
NOTE!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the
control keys [Hand On] – [Auto On].
[Reset]
is used for resetting the adjustable frequency drive after an alarm (trip). It can be selected as
Enable
[1] or
Disable
[0] via par. 0-43
[Reset] Key on LCP
.
The parameter shortcut
can be carried out by holding down the [Main Menu] key for 3 seconds.
The parameter shortcut allows direct access to any parameter.
2.2.2 Numeric Local Control Panel (NLCP)
See the FC Series Instruction Manual for instructions for using the numeric LCP.
2 Operator Interface and Adjustable Frequen-
cy Drive Control
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
2-6
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
2
Summary of Contents for VLT HVAC FC 100
Page 219: ......