Voltage (AC)
FC 102
FC202
FC 302
Resistance (Ohms)
380-500
P110
P110
P90K
4.5
380-500
P132
P132
P110
3.8
380-500
P160
P160
P132
3.1
380-500
P200
P200
P160
2.6
380-500
P250
P250
P200
5.1
380-500
P315
P315
P250
4.2
380-500
P355
P355
P315
2.6
380-500
P400
P400
P355
2.6
380-500
P450
P450
P400
2.3
525-690
P45K
P45K
P37K
5.9
525-690
P55K
P55K
P45K
5.9
525-690
P75K
P75K
P55K
5.9
525-690
P90K
P90K
P75K
5.9
525-690
P110
P110
P90K
5.9
525-690
P132
P132
P110
5.9
525-690
P160
P160
P132
4.5
525-690
P200
P200
P160
3.1
525-690
P250
P250
P200
3.1
525-690
P315
P315
P250
2.6
525-690
P400
P400
P315
5.1
525-690
P450
P450
P355
4.5
525-690
P500
P500
P400
4.5
525-690
P560
P560
P500
3.8
525-690
P630
P630
P560
2.6
Table 6.2: Scaling Card Resistance Values
6.3.15 Fan Tests
The fan control circuit is made up of the fan transformer and the control circuitry located on the
power card along with control signals for ON, OFF, and speed control from the control card. Since
the fans do not necessarily run at all times, see the description for cooling fan operation under
sequence of operation in Section 3.3.5.
Supply voltage
Supply voltage for the fans is from the soft charge card to power card connector
MK106. First, verify the supply voltage is present as follows.
1.
Use a voltmeter to measure the AC phase to phase voltage at R, S, and T of power card
connector MK106. It should equal main supply voltage applied to adjustable frequency
drive.
2.
If voltage is not present, ensure proper AC line voltage is applied to adjustable frequency
drive. Conduct Input Voltage test (6.3.2).
3.
If AC line voltage is present at the input of the adjustable frequency drive but not at
MK106 of the power card, conduct a static test of the soft charge fuses (6.2.1).
4.
If voltage is present at MK106, check the voltage at the fan transformer read from con-
nector CN2 located near the transformer. With a voltmeter, read the AC voltage at CN2
pins 1 and 3. The voltage should correspond to the main AC line voltage applied to the
adjustable frequency drive.
5.
If voltage is not present, ensure jumpers are in place at power card connector FK103.
Otherwise, connect an external source of power to terminal FK103 for fan supply voltage.
If the jumpers are in place or an auxiliary supply is connected and powered but no voltage is
present at the fan transformer connector CN2, the power card is likely defective. Replace the
power card in accordance with the disassembly instructions in Section 7 or 8.
6 Test Procedures
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
6-36
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
6