WARNING/ALARM 35, Out of frequency range:
This warning is active if the output frequency has reached the high limit (set in parameter 4-53)
or low limit (set in parameter 4-52). In
Process Control, Closed-loop
, par. 1-00
Configuration
Mode
, this warning is displayed.
WARNING/ALARM 36, Mains failure
This warning/alarm is only active if the supply voltage to the adjustable frequency drive is lost
and par. 14-10
Line Failure
is NOT set to OFF. Check the fuses to the adjustable frequency drive
ALARM 38, Internal fault
It may be necessary to contact your Danfoss supplier. Some typical alarm messages:
0
Serial port cannot be initialized. Serious
hardware failure
256-258 Power EEPROM data is defective or too old
512
Control board EEPROM data is defective or
too old
513
Communication time out reading EEPROM
data
514
Communication time out reading EEPROM
data
515
Application Orientated Control cannot rec-
ognize the EEPROM data
516
Cannot write to the EEPROM because a
write command is on progress
517
Write command is under timeout
518
Failure in the EEPROM
519
Missing or invalid Barcode data in EEPROM
783
Parameter value outside of min/max limits
1024-12
79
A CAN message that must be sent, couldn't
be sent
1281
Digital Signal Processor flash timeout
1282
Power micro software version mismatch
1283
Power EEPROM data version mismatch
1284
Cannot read Digital Signal Processor soft-
ware version
1299
Option SW in slot A is too old
1300
Option SW in slot B is too old
1301
Option SW in slot C0 is too old
1302
Option SW in slot C1 is too old
1315
Option SW in slot A is not supported (not
allowed)
1316
Option SW in slot B is not supported (not
allowed)
1317
Option SW in slot C0 is not supported (not
allowed)
1318
Option SW in slot C1 is not supported (not
allowed)
1379
Option A did not respond when calculating
Platform Version.
1380
Option B did not respond when calculating
Platform Version.
1381
Option C0 did not respond when calculating
Platform Version.
1382
Option C1 did not respond when calculating
Platform Version.
1536
An exception in the Application Orientated
Control is registered. Debug information
written in LCP
1792
DSP watchdog is active. Debugging of
power part data Motor Orientated Control
data not transferred correctly
2049
Power data restarted
2064-207
2
H081x: option in slot x has restarted
2080-208
8
H082x: option in slot x has issued a pow-
er-up wait
2096-210
4
H083x: option in slot x has issued a legal
power-up wait
2304
Could not read any data from power EE-
PROM
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missing io_statepage from power unit
2324
The power card configuration is deter-
mined to be incorrect at power-up
2325
A power card has stopped communicating
while main power is applied
2326
The power card configuration is deter-
mined to be incorrect after the power
card register delay.
2327
Too many power card locations have
been registered as present.
2330
Power size information between the pow-
er cards does not match.
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP
(state running)
2816
Stack overflow of control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP Stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool to small
3072-512
2
Parameter value is outside its limits
5123
Option in slot A: Hardware incompatible
with control board hardware
5124
Option in slot B: Hardware incompatible
with control board hardware
5125
Option in slot C0: Hardware incompatible
with control board hardware
5126
Option in slot C1: Hardware incompatible
with control board hardware
5376-623
1
Out of memory
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on the power card. The problem could
be on the power card, on the gate drive card, or the ribbon cable between the power card and
gate drive card.
High Power Service Manual for VLT
®
FC Series
Adjustable Frequency Drives
4 Troubleshooting
MG.90.L1.22 - VLT
®
is a registered Danfoss trademark
4-15
4