Decentral Solutions
Par. 316
Terminal 60, max. scaling
= 20 mA
■
4-20 mA reference
4-20 mA reference on terminal 60 and speed
feedback signal on terminal 53.
Par. 100
Configuration
=
Speed closed loop
[1]
Par. 308
Analog input
=
Feedback
[2]
Par. 309
Terminal 53, min. scaling
= 0 Volt
Par. 310
Terminal 53, max. scaling
= 10 Volt
Par. 314
Analog input
=
Reference
[1]
Par. 309
Terminal 60, min. scaling
= 4 mA
Par. 310
Teminal 60, max. scaling
= 20 mA
■
50 Hz counter-clockwise to 50 Hz clockwise.
With internally supplied potentiometer.
Par. 100
Configuration
=
Speed regulation
open loop
[0]
Par. 200
Output frequency range
=
Both
directions, 0-132 Hz
[1]
Par. 203
Reference range
=
Min. ref. - Max. ref.
[0]
Par. 204
Min. reference
= - 50 Hz
Par. 205
Max. reference
= 50 Hz
Par. 302
Digital input
=
Start
[7]
Par. 304
Digital input
=
Coasting stop inverted
[2]
Par. 308
Analog input
=
Reference
[1]
Par. 309
Terminal 53, min. scaling
= 0 Volt.
Par. 310
Terminal 53, max. scaling
= 10 Volt.
■
Preset references
Switch between 8 preset references via two digital
inputs and Setup 1 and Setup 2.
Par. 004
Active Setup
=
Multisetup 1
[5]
Par. 204
Min. reference
= 0 Hz
Par. 205
Max. reference
= 50 Hz
Par. 302
Digital input
=
Start
[7]
Par. 303
Digital input
= Choice of Setup, lsb [31]
Par. 304
Digital input
=
Coasting stop inverted
[2]
Par. 305
Digital input
= Preset ref., lsb [22]
Par. 307
Digital input
= Preset ref., msb [23]
Setup 1
contains the following preset references:
MG.90.F2.22 - VLT is a registered Danfoss trademark
90