Decentral Solutions
Programming, FCD
300
External reference [%]
gives the sum of external
references as a percentage (sum of analog/pulse/serial
communication) in the range from Minimum reference,
Ref
MIN
to Maximum reference, Ref
MAX
.
Status word [Hex]
gives one or several status
conditions in a Hex code. See
Serial communication
in the
Design Guide
for further information.
Heat sink temp.[°C]
gives the present heat sink
temperature of the variable frequency drive. The
cut-out limit is 194-212 °F (90-100 °C), while cutting
back in occurs at 158 ± 10% °F (70 ± 5 °C).
Alarm word [Hex]
gives one or several alarms
in hex code. See
Serial communication
in the
Design Guide
for further information.
Control word [Hex]
gives the control word for the
variable frequency drive. See
Serial communication
in the
Design Guide
for further information.
Warning word [Hex]
gives one or several warnings
in hex code. See
Serial communication
in the
Design Guide
for further information.
Extended status word [Hex]
gives one or several status
modes in Hex code. See
Serial communication
in
the
Design Guide
for further information.
Communication option card warning [Hex]
gives a
warning word if there is a fault in the communication
bus. Only active if communication options are installed.
If there are no communication options 0
Hex is displayed.
Pulse input 29[Hz]
gives the frequency in Hz
connected to terminal 29.
Pulse count
gives the number of pulses that
the unit has registered.
010 Small display line 1.1
(DISPLAY LINE 1.1)
Value:
See par. 009
Large display readout
✭
Reference [%] [1]
Function:
In this parameter, the first of three data values
can be selected that is to be displayed in the LCP
control unit display, line 1, position 1. This is a useful
function, e.g. when setting the PID regulator, as
it gives a view of process reactions to reference
changes. The display readout is activated by
pushing the [DISPLAY STATUS] key.
Description of choice:
See parameter 009
Large display readout
.
011 Small display readout 1.2
(DISPLAY LINE 1.2)
Value:
See parameter 009
Large display readout
✭
Motor current [A][6]
Function:
See the functional description given under parameter
010
Small display readout
.
Description of choice:
See parameter 009
Large display readout
.
012 Small display readout 1.3
(DISPLAY LINE 1.3)
Value:
See parameter 009
Large display readout
✭
Power [kW][8]
Function:
See the functional description given under parameter
010
Small display readout
.
Description of choice:
See parameter 009
Large display readout
.
013 Local control
(LOC CTRL/CONFIG.)
Value:
Local not active (DISABLE)
[0]
Local control and open loop
(LOC CTRL/OPEN LOOP)
[1]
Remote-operated control and open loop
(LOC+DIG CTRL)
[2]
Local control as parameter 100
(LOC CTRL/AS P100)
[3]
✭
Remote-operated control as parameter 100
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.90.F2.22 - VLT is a registered Danfoss trademark
103