Decentral Solutions
Installation, FCD
300
■
AC lines and motor connection with service switch
■
Connection of HAN 10E motor plug for T73
HAN 10E pin no 1 - Motor phase U
HAN 10E pin no 2 - Motor phase V
HAN 10E pin no 3 - Motor phase W
HAN 10E pin no 4 - Motor brake, see
Operating
Instructions MG.04.BX.YY
, terminal 122
HAN 10E pin no 5 - Motor brake, see
Operating
Instructions MG.04.BX.YY
, terminal 123
HAN 10E pin no 9 - Motor thermistor, see
Operating
Instructions MG.04.BX.YY
, terminal 31A
HAN 10E pin no 10 - Motor thermistor, see
Operating Instructions MG.04.BX.YY
, terminal 31B
PE = protective ground
■
Parallel connection of motors
The variable frequency drive is able to control
several motors connected in parallel. If the motors
are to have different rpm values, use motors with
different rated rpm values. Motor rpm is changed
simultaneously, which means that the ratio between
the rated rpm values is maintained across the range.
The total current consumption of the motors is
not to exceed the maximum rated output current
I
INV
for the variable frequency drive.
Problems may arise at the start and at low rpm
values if the motor sizes are widely different. This
is because the small motors
’
relatively high ohmic
resistance in the stator calls for a higher voltage
at the start and at low rpm values.
In systems with motors connected in parallel, the
electronic thermal relay (ETR) of the variable frequency
drive cannot be used as motor protection for the
individual motor. For this reason further motor
protection must be used, e.g. thermistors in each
motor (or an individual thermal relay).
NOTE
Parameter 107
Automatic motor tuning, AMT
cannot be used when motors are connected
in parallel. Parameter 101
Torque characteristic
must be set to
Special motor characteristics
[8]
when motors are connected in parallel.
■
Motor cables
See Technical data for correct sizing of motor cable
cross-section and length. Always comply with national
and local regulations on cable cross-section.
MG.90.F2.22 - VLT is a registered Danfoss trademark
83