Decentral Solutions
319 Analog output terminal 42
(AO 42 FUNCTION)
Value:
No function (NO OPERATION)
[0]
External reference min.-max. 0-20 mA
(REF MIN-MAX = 0-20 MA)
[1]
External reference min.-max. 4-20 mA
(REF MIN-MAX = 4-20 MA)
[2]
Feedback min.-max. 0-20 mA
(FB MIN-MAX = 0-20 MA)
[3]
Feedback min.-max. 4-20 mA
(FB MIN-MAX = 4-20 MA)
[4]
Output frequency 0-max 0-20 mA
(0-FMAX = 0-20 MA)
[5]
Output frequency 0-max 4-20 mA
(0-FMAX = 4-20 MA)
[6]
✭
Output current 0-I
INV
0-20 mA
(0-IMAX = 0-20 MA)
[7]
Output current 0-I
IINV
4-20 mA
(0-PNOM = 4-20 MA)
[8]
Output power 0-P
M,N
0-20 mA
(0-PNOM = 0-20 MA)
[9]
Output power 0-P
M,N
4-20 mA
(0-PNOM = 4-20 MA)
[10]
Inverter temperature 68-212 °F (20-100 °C) 0-20 mA
(TEMP 20-100 C=0-20 MA)
[11]
Inverter temperature 68-212 °F (20-100 °C) 4-20 mA
(TEMP 20-100 C=0-20 MA)
[12]
Function:
The analog output can be used for stating a process
value. It is possible to choose two types of output
signals 0 - 20 mA or 4 - 20 mA.
If used as a voltage output (0 - 10 V), a pull-down
resistor of 500
must be fitted to common
(terminal 55). If the output is used as a current
output the resulting resistance from the equipment
connected may not exceed 500
.
Description of choice:
No function
. Is selected if the analog output
is not to be used.
External Ref
MIN
- Ref
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional
to the resulting reference value in the interval
Minimum reference, Ref
MIN
- Maximum reference,
Ref
MAX
(parameters 204/205).
FB
MIN
-FB
MAX
0-20 mA/ 4-20 mA.
An output signal is obtained, which is proportional to the
feedback value in the interval Minimum feedback, FB
MIN
- Maximum feedback, FB
MAX
(parameter 414/415).
0-f
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to
the output frequency in the interval 0 - f
MAX
(parameter
202
Output frequency, high limit, f
MAX
).
0 - I
INV
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional
to the output current in the interval 0 - I
INV
0 - P
M,N
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to
the present output power. 20 mA corresponds to the
value set in parameter 102
Motor power, P
M,N
.
0 - Temp.
MAX
0-20 mA/4-20 mA.
An output signal is obtained, which is proportional to
the present heatsink temperature. 0/4 mA corresponds
to a heatsink temperature of less than 68 °F (20 °C),
and 20 mA corresponds to 212 °F (20 °C).
323 Relay output 1-3
(RELAY 1-3 FUNCT.)
Value:
✭
No function (NO OPERATION)
[0]
Unit ready (UNIT READY)
[1]
Enable/no warning (ENABLE/NO WARNING)
[2]
Running (RUNNING)
[3]
Running in reference, no warning
( RUN ON REF/NO WARN)
[4]
Running, no warnings
(RUNNING/NO WARNING)
[5]
Running in reference range, no warnings
(RUN IN RANGE/ NO WARN)
[6]
Ready - AC line voltage within range
(RDY NO OVER/UNDERVOL)
[7]
Alarm or warning
(ALARM OR WARNING)
[8]
Current higher than current limit, par. 221
(CURRENT LIMIT)
[9]
Alarm (ALARM)
[10]
Output frequency higher than f
LOW
par. 225
(ABOVE FREQUENCY LOW)
[11]
Output frequency lower than f
HIGH
par. 226
(BELOW FREQUENCY HIGH)
[12]
Output current higher than I
LOW
par. 223
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.90.F2.22 - VLT is a registered Danfoss trademark
132