Decentral Solutions
■
Electrical connection
No. 91 92
93
AC line voltage 3 x 380-480 V
L1 L2
L3
PE
Ground connection
NOTE
Please check that the AC line voltage fits the
mains voltage of the frequency converter, which
can be seen from the nameplate.
See
Technical data
for correct dimensioning
of cable cross-section.
■
Pre-fuses
See
Technical data
for correct dimensioning
of pre-fuses.
■
Motor connection
Connect the motor to terminals 96, 97, 98.
Connect ground to PE-terminal.
No. 96
97
98
Motor voltage 0-100% of AC
line voltage
U
V
W
3 wires out of motor
U1
W2
V1
U2
W1
V2
6 wires out of motor, Delta
connected
U1 V1
W1 6 wires out of motor, Star
connected
U2, V2, W2 to be
interconnected separately
(optional terminal block)
PE
Ground connection
See
Technical data
for correct dimensioning
of cable cross-section.
All types of three-phase asynchronous standard
motors can be connected to a variable frequency drive.
Normally, small motors are star-connected (230/400 V,
/ Y). Large motors are delta-connected (400/690
V,
/ Y). The correct connection mode and voltage
can be read from the motor nameplate.
NOTE
In motors without phase insulation paper,
an LC filter should be fitted on the output
of the variable frequency drive.
■
Direction of motor rotation
The factory setting is for clockwise rotation
with the variable frequency drive transformer
output connected as follows:
Terminal 96 connected to U-phase.
Terminal 97 connected to V-phase.
Terminal 98 connected to W-phase.
The direction of rotation can be changed by switching
two phases on the motor terminals.
MG.90.F2.22 - VLT is a registered Danfoss trademark