The Start-up quick guide for compressor functions
28-13 Boost Duration
60 s
5
28-01 Interval between Starts
130BD874.12
28-02 Minimum Run Time
3
28-00 Short Cycle Protection
[1]
Enabled
1
28-10 Oil Return Management
[1]
On
4
2
300 s
60 s
Illustration 6.3 Compressor Function Quick Guide
Compressor function quick guide
Parameter
Option
Default
Function
Parameter 28-00 Short Cycle
Protection
[0] Disabled
[1] Enabled
[1] Enabled
Select if short cycle protection is to be used.
Parameter 28-01 Interval between
Starts
0–3600 s
300 s
Enter the minimum allowed time between
starts.
Parameter 28-02 Minimum Run Time
10–3600 s
60 s
Enter the minimum allowed time to run
before stop.
Parameter 28-10 Oil Return
Management
[0] Off
[1] On
[1] On
Select if oil return management is to be used.
Parameter 28-13 Boost Duration
60–300 s
60 s
Enter the boost duration for the oil return.
Table 6.5 Compressor Function