7.11.3 Bus Speed Reference Value
Speed reference value is transmitted to the frequency
converter in a relative value in %. The value is transmitted
in the form of a 16-bit word. The integer value 16384
(4000 hex) corresponds to 100%. Negative figures are
formatted using 2’s complement. The actual output
frequency (MAV) is scaled in the same way as the bus
reference.
Actual output
frequency
STW
Follower-slave
Speed reference
CTW
Master-slave
16bit
130BA276.11
Illustration 7.16 Actual Output Frequency (MAV)
The reference and MAV are scaled as follows:
Reverse
Forward
Par.3-00 set to
(1) -max- +max
Max reference
Max reference
Par.3-00 set to
(0) min-max
Max reference
Forward
Min reference
100%
(4000hex)
-100%
(C000hex)
0%
(0hex)
Par.3-03
0
Par.3-03
Par.3-03
(4000hex)
(0hex)
0%
100%
Par.3-02
130BA277.10
Illustration 7.17 Reference and MAV
RS485 Installation and Set-...
VLT
®
Compressor Drive CDS 803
68
Danfoss A/S © 12/2015 All rights reserved.
MG18N202