5.1.3 Side-by-side Installation
The frequency converter can be mounted side-by-side but requires the clearance above and below for cooling.
Power [kW(hp)]
Clearance above/below [mm(in)]
Size
IP class
3x200–240 V
3x380–480 V
H3
IP20
3.7 (5)
5.5–7.5 (7.5–10)
100 (4)
H4
IP20
5.5–7.5 (7.5–10)
11–15 (15–20)
100 (4)
H5
IP20
11 (15)
18.5–22 (25–30)
100 (4)
Table 5.3 Clearance Required for Cooling
NOTICE
With IP21/NEMA Type1 option kit mounted, a distance of 50 mm (2 in) between the units is required.
5.1.4 Field Mounting
For field mounting, IP21/NEMA Type 1 kits are
recommended.
How to Install
VLT
®
Compressor Drive CDS 803