8.1.2 Mains Supply 3x380–480 V AC
Frequency converter
4 TR/VZH028
5 TR/VZH035
6.5 TR/VZH044
Typical shaft output [kW]
6.0
7.5
10
IP20 enclosure protection rating
H3
H3
H4
Maximum cable size in terminals (mains, compressor) [mm
2
/AWG]
4/10
4/10
16/6
Output current
Continuous (3x380–440 V) [A]
11.6
14.3
16.4
Intermittent (3x380–440 V) [A]
–
–
18.0
Continuous (3x440–480 V) [A]
9.8
12.3
15.5
Intermittent (3x440–480 V) [A]
–
–
17.0
Maximum input current
Continuous (3x380–440 V) [A]
12.7
15.1
18.0
Intermittent (3x380–440 V) [A]
–
–
19.8
Continuous (3x440–480 V) [A]
10.8
12.6
17.0
Intermittent (3x440–480 V) [A]
–
–
18.7
Maximum mains fuses
Estimated power loss [W],
best case/typical
1)
104/131
159/198
248/274
Weight enclosure protection IP20 [kg/(lb)]
4.3 (9.5)
4.5 (9.9)
7.9 (17.4)
Efficiency [%],
best case/typical
1)
98.4/98.0
98.2/97.8
98.1/97.9
Table 8.2 3x380–480 V AC
1) At rated load conditions.
General Specifications
VLT
®
Compressor Drive CDS 803
70
Danfoss A/S © 12/2015 All rights reserved.
MG18N202
8
8