D. Operation keys and indicator lights
13 [Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTICE
[2] coast inverse
is the default option for
parameter 5-12 Terminal 27 Digital Input
. If there is
no 24 V supply to terminal 27, [Hand On] does not
start the motor. Connect terminal 12 to terminal 27.
14 [Off/Reset]: Stops the motor (Off). If in alarm mode, the
alarm is reset.
15 [Auto On]: The frequency converter is controlled either via
control terminals or serial communication.
Table 6.3 Legend to
, Part III
6.3 Menus
6.3.1 Status Menu
In the
Status
menu, the selection options are:
•
Motor frequency [Hz],
parameter 16-13 Frequency
.
•
Motor current [A],
parameter 16-14 Motor current
.
•
Motor speed reference in percentage [%],
parameter 16-02 Reference [%]
.
•
Feedback,
parameter 16-52 Feedback[Unit]
.
•
Motor power
parameter 16-10 Power [kW]
for kW,
parameter 16-11 Power [hp]
for hp. If
parameter 0-03 Regional Settings
is set to
[1] North
America
, motor power is shown in hp instead of
kW.
•
Custom readout
parameter 16-09 Custom Readout
.
6.3.2 Quick Menu
Use the Quick Menu to program the most common
functions. The Quick Menu consists of:
•
Quick guide for open-loop applications.
•
Closed-loop set-up quick guide.
•
Changes made.
•
Compressor functions.
How to Program
Design Guide
MG18N202
Danfoss A/S © 12/2015 All rights reserved.
39