11.11.2 Status Word According to FC Profile
Output frequency
STW
Bit
Slave-master
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
130BA273.12
Illustration 11.17 STW Slave-to-Master
Bit
Bit=0
Bit=1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
No error
Error (no trip)
05
Reserved
–
06
No error
Triplock
07
No warning
Warning
08
Speed
≠
reference
Speed=reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit OK
11
No operation
In operation
12
Drive OK
Stopped, auto start
13
Voltage OK
Voltage exceeded
14
Torque OK
Torque exceeded
15
Timer OK
Timer exceeded
Bit 00, Control not ready/ready
Bit 00=0: The drive trips.
Bit 00=1: The drive controls are ready, but the power
component does not necessarily receive any supply in the
case of a 24 V external supply to the controls.
Bit 01, Drive ready
Bit 01=1: The drive is ready for operation but the coasting
command is active via the digital inputs or via serial
communication.
Bit 02, Coasting stop
Bit 02=0: The drive releases the motor.
Bit 02=1: The drive starts the motor with a start command.
Bit 03, No error/trip
Bit 03=0: The drive is not in fault mode.
Bit 03=1: The drive trips. To re-establish operation, press
[Reset].
Bit 04, No error/error (no trip)
Bit 04=0: The drive is not in fault mode.
Bit 04=1: The drive shows an error but does not trip.
Bit 05, Not used
Bit 05 is not used in the status word.
Bit 06, No error/triplock
Bit 06=0: The drive is not in fault mode.
Bit 06=1: The drive is tripped and locked.
Bit 07, No warning/warning
Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
Bit 08, Speed≠ reference/speed=reference
Bit 08=0: The motor is running, but the present speed is
different from the preset speed reference. For example,
when the speed ramps up/down during start/stop.
Bit 08=1: The motor speed matches the preset speed
reference.
Bit 09, Local operation/bus control
Bit 09=0: [Stop/reset] is activated on the control unit or
[2]
Local
in
parameter 3-13 Reference Site
is selected. The drive
cannot be controlled via serial communication.
Bit 09=1 It is possible to control the drive via the fieldbus/
serial communication.
Bit 10, Out of frequency limit
Bit 10=0: The output frequency has reached the value in
parameter 4-11 Motor Speed Low Limit [RPM]
or
parameter 4-13 Motor Speed High Limit [RPM]
.
Bit 10=1: The output frequency is within the defined limits.
Bit 11, No operation/in operation
Bit 11=0: The motor is not running.
Bit 11=1: The drive has a start signal or the output
frequency is greater than 0 Hz.
Bit 12, Drive OK/stopped, autostart
Bit 12=0: There is no temporary overtemperature on the
inverter.
Bit 12=1: The inverter stops because of overtemperature
but the unit does not trip and resumes operation once the
overtemperature stops.
Bit 13, Voltage OK/limit exceeded
Bit 13=0: There are no voltage warnings.
Bit 13=1: The DC voltage in the DC link is too low or too
high.
Bit 14, Torque OK/limit exceeded
Bit 14=0: The motor current is lower than the torque limit
selected in
parameter 4-18 Current Limit
.
Bit 14=1: The torque limit in
parameter 4-18 Current Limit
is
exceeded.
Bit 15, Timer OK/limit exceeded
Bit 15=0: The timers for motor thermal protection and
thermal protection are not exceeded 100%.
Bit 15=1: One of the timers exceeds 100%.
If the connection between the InterBus option and the
drive is lost, or an internal communication problem has
occurred, all bits in the STW are set to 0.
Appendix
VLT® AutomationDrive FC 361
90