Terminal
Parameter
Default
setting
Description
61
–
–
Integrated RC-filter to
connect cable shield
if there are EMC
problems.
68 (+)
Parameter
group 8-3* FC
Port Settings
–
RS485 interface. A
switch (BUS TER.) is
provided on the
control card for bus
termination
resistance.
69 (-)
Parameter
group 8-3* FC
Port Settings
–
Table 7.2 Serial Communication Terminal Descriptions
Terminal
Parameter
Default
setting
Description
12, 13
–
+24 V DC 24 V DC supply
voltage for digital
inputs and external
transducers.
Maximum output
current 200 mA for all
24 V loads.
18
Parameter 5-10
Terminal 18
Digital Input
[8] Start
Digital inputs.
19
Parameter 5-11
Terminal 19
Digital Input
[10]
Reversing
32
Parameter 5-14
Terminal 32
Digital Input
[0] No
operation
33
Parameter 5-15
Terminal 33
Digital Input
[0] No
operation
27
Parameter 5-12
Terminal 27
Digital Input
[2] Coast
inverse
For digital input or
output. Default
setting is input.
29
Parameter 5-13
Terminal 29
Digital Input
[14] JOG
20
–
–
Common for digital
inputs and 0 V
potential for 24 V
supply.
Table 7.3 Digital Input/Output Terminal Descriptions
Terminal
Parameter
Default
setting
Description
39
–
–
Common for analog
output.
42
Parameter 6-50
Terminal 42
Output
[0] No
operation
Programmable analog
output. 0–20 mA or
4–20 mA at a
maximum of 500
Ω
.
50
–
+10 V DC 10 V DC analog
supply voltage for
potentiometer or
thermistor. 15 mA
maximum.
53
Parameter
group 6-1*
Analog Input 1
Reference Analog input. For
voltage or current.
Switches A53 and
A54 select mA or V.
54
Parameter
group 6-2*
Analog Input 2
Feedback
55
–
–
Common for analog
input.
Table 7.4 Analog Input/Output Terminal Descriptions
Relay terminals
RELAY 1
RELAY 2
01 02 03
04 05 06
130BF156.10
Illustration 7.8 Relay 1 and Relay 2 Terminals
•
Relay 1 and relay 2. Location depends on drive
configuration. See the
operating guide
.
•
Terminals on built-in optional equipment. See the
instructions provided with the equipment option.
Terminal
Parameter
Default
setting
Description
01, 02, 03
Parameter 5-40
Function Relay
[0]
[0] No
operation
Form C relay output.
For AC or DC voltage
and resistive or
inductive loads.
04, 05, 06
Parameter 5-40
Function Relay
[1]
[0] No
operation
Table 7.5 Relay Terminal Descriptions
Electrical Installation Con...
Design Guide
MG06K102
Danfoss A/S © 03/2019 All rights reserved.
43
7
7