4 Options and Accessories Overview
4.1 Fieldbus Devices
This section describes the fieldbus devices that are
available with the VLT
®
AutomationDrive FC 361 series.
Using a fieldbus device reduces system cost, delivers faster
and more efficient communication, and provides an easier
user interface. For ordering numbers, refer to
chapter 10.2 Ordering Numbers for Options and Accessories
.
4.1.1 VLT
®
PROFIBUS DP-V1 MCA 101
The VLT
®
PROFIBUS DP-V1 MCA 101 provides:
•
Wide compatibility, a high level of availability,
support for all major PLC vendors, and compati-
bility with future versions.
•
Fast, efficient communication, transparent instal-
lation, advanced diagnosis, and parameterization
and auto-configuration of process data via a GSD
file.
•
Acyclic parameterization using PROFIBUS DP-V1,
PROFIdrive, or Danfoss FC profile state machines.
4.1.2 VLT
®
PROFINET MCA 120
The VLT
®
PROFINET MCA 120 combines the highest
performance with the highest degree of openness. The
option is designed so that many of the features from the
VLT
®
PROFIBUS MCA 101 can be reused, minimizing user
effort to migrate PROFINET and securing the investment in
a PLC program.
•
Same PPO types as the VLT
®
PROFIBUS DP V1
MCA 101 for easy migration to PROFINET.
•
Built-in web server for remote diagnosis and
reading out of basic drive parameters.
•
Supports MRP.
•
Supports DP-V1. Diagnostic allows easy, fast, and
standardized handling of warning and fault
information into the PLC, improving bandwidth in
the system.
•
Implementation in accordance with Conformance
Class B.
4.2 Functional Extensions
This section describes the functional extension options that
are available with the VLT
®
AutomationDrive FC 361 series.
For ordering numbers, refer to
Numbers for Options and Accessories
.
4.2.1 VLT
®
General Purpose I/O Module
MCB 101
The VLT
®
General Purpose I/O Module MCB 101 offers an
extended number of control inputs and outputs:
•
3 digital inputs 0–24 V: Logic 0 < 5 V; Logic 1 >
10 V.
•
2 analog inputs 0–10 V: Resolution 10 bits plus
sign.
•
2 digital outputs NPN/PNP push-pull.
•
1 analog output 0/4–20 mA.
•
Spring-loaded connection.
4.2.2 VLT
®
Encoder Input MCB 102
The MCB 102 option offers the possibility to connect
various types of incremental and absolute encoders. The
connected encoder can be used for closed-loop speed
control and closed-loop flux motor control.
The following encoder types are supported:
•
5 V TTL (RS 422).
•
1VPP SinCos.
4.2.3 VLT
®
Resolver Option MCB 103
The MCB 103 option enables connection of a resolver to
provide speed feedback from the motor.
•
Primary voltage: 2–8 V
rms
.
•
Primary frequency: 2.0–15 kHz.
•
Primary maximum current: 50 mA rms.
•
Secondary input voltage: 4 V
rms
.
•
Spring-loaded connection.