Ambient conditions
Enclosure sizes J1–J7
IP20
Vibration test, all enclosure sizes
1.0 g
Relative humidity
5–95% (IEC 721-3-3); Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
Class Kd
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
Maximum 55
°
C (131
°
F)
1)
- at full continuous output current with some power size
Maximum 50
°
C (122
°
F)
- at full continuous output current
Maximum 45
°
C (113
°
F)
Minimum ambient temperature during full-scale operation
0
°
C (32
°
F)
Minimum ambient temperature at reduced performance
-10
°
C (14
°
F)
Temperature during storage/transport
-25 to +65/70
°
C (-13 to +149/158
°
F)
Maximum altitude above sea level without derating
1000 m (3281 ft)
Maximum altitude above sea level with derating
3000 m (9843 ft)
EMC standards, emission
EN 61800-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11,
EN 61000-3-12, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2,
EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Energy efficiency class
1)
IE2
1) Determined according to EN 50598-2 at:
•
Rated load.
•
90% rated frequency.
•
Switching frequency factory setting.
•
Switching pattern factory setting.
Control card performance
Scan interval
1 ms
Protection and features
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heat sink ensures that the frequency converter trips when the temperature reaches
a predefined level. An overload temperature cannot be reset until the temperature of the heat sink is below the
temperature limit.
•
The frequency converter is protected against short circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load and
parameter setting).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips when the intermediate
circuit voltage is too low or too high.
•
The frequency converter is protected against ground faults on motor terminals U, V, W.
Specifications