5.4.4 Status Menu on NLCP
After power-up, Status Menu is active. Press [Menu] to
toggle between
Status
,
Quick Menu
, and
Main Menu
.
[
▲
] and [
▼
] toggle between the options in each menu.
The display indicates the status mode with a small arrow
above
Status
.
130BA466.10
Illustration 5.6 Indicating Status Mode
The following 8 parameters can be accessed from NLCP
status menu in auto-on mode:
•
Parameter 16-02 Reference [%]
.
•
Parameter 16-09 Custom Readout
.
•
Parameter 16-10 Power [kW]
.
•
Parameter 16-13 Frequency
.
•
Parameter 16-14 Motor current
.
•
Parameter 16-16 Torque [Nm]
.
•
Parameter 16-30 DC Link Voltage
.
•
Parameter 16-52 Feedback[Unit]
.
The following 6 parameters can be accessed from NLCP
status menu in [Hand On] mode:
•
Parameter 16-09 Custom Readout
.
•
Parameter 16-10 Power [kW]
.
•
Parameter 16-13 Frequency
.
•
Parameter 16-14 Motor current
.
•
Parameter 16-16 Torque [Nm]
.
•
Parameter 16-30 DC Link Voltage
.
5.4.5 Main Menu on NLCP
The
Main Menu
gives access to all parameters.
1.
To enter
Main Menu
, press [Menu] until the
indicator in the display is placed above
Main
Menu
.
2.
[
▲
] [
▼
]: Browse through the parameter groups.
3.
Press [OK] to select a parameter group.
4.
[
▲
] [
▼
]: Browse through the parameters in the
specific group.
5.
Press [OK] to select the parameter.
6.
[
►
] and [
▲
] [
▼
]: Set/change the parameter value.
7.
Press [OK] to accept the value.
8.
To exit, press either [Back] twice (or 3 times for
array parameters) to enter
Main Menu
, or press
[Menu] once to enter
Status
.
See
, and
for the
principles of changing the value of continuous,
enumerated, and array parameters, respectively. The
actions in the illustrations are described in
, and
.
Commissioning
Quick Guide
MG06A702