Parameter 6-91 Terminal 42 Analog
Output
[103] Motor Current
Parameter 7-00 Speed PID Feedback
Source
[1] 24 V encoder
Table 6.4 Speed Close Loop
Application
Industrial washing machines, conveyors.
Parameter 0-16 Application Selection
is set to
[5] Multi Speed
.
Description
For applications with 8 different speeds by digital input. By using
another digital input, 16 speeds are possible.
130BC434.11
+24V 12
DI1
18
DI2
19
DI3
27
DI4
29
DI5
3
2
DI6
3
3
DI7
3
1
COM 20
+10V 50
AI1
53
AI2
54
COM 55
AO1 4
5
AO2 4
2
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Pre set ref bit 0
Pre set ref bit 1
Pre set ref bit 2
Parameter settings
Parameter
Option/value
Parameter 1-00 Configuration Mode
[0] Speed Open Loop
Parameter 3-00 Reference Range
[0] Min–Max
Parameter 3-15 Reference 1 Source
[0] No Function
Parameter 4-14 Motor Speed High Limit
[Hz]
50.0 Hz
Parameter 5-10 Terminal 18 Digital Input
[8] Start
Parameter 5-12 Terminal 27 Digital Input
[2] Coast Inverse
Parameter 5-13 Terminal 29 Digital Input
[16] Preset ref bit 0
Parameter 5-14 Terminal 32 Digital Input
[17] Preset ref bit 1
Parameter 5-15 Terminal 33 Digital Input
[18] Preset ref bit 2
Parameter 6-70 Terminal 45 Mode
[0] 0–20 mA
Parameter 6-71 Terminal 45 Analog
Output
[100] Output frequency
Parameter 6-90 Terminal 42 Mode
[0] 0–20 mA
Parameter 6-91 Terminal 42 Analog
Output
[103] Motor Current
Table 6.5 Multi-speed
Applications
VLT
®
AutomationDrive FC 360
40
Danfoss A/S © 03/2017 All rights reserved.
MG06A702
6
6