![background image](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive-fc-302/vlt-automationdrive-fc-302_design-manual_3434520193.webp)
(
Parameter 5-12 Terminal 27 Digital Input
[2]
Coasting Stop, Inverse
).
•
Terminal 29 output
(
Parameter 5-02 Terminal 29 Mode
[1] Terminal 29
Mode Output
and
parameter 5-31 Terminal 29
Digital Output
[27] Torque limit & stop
).
•
Relay output [0] (Relay 1)
(
Parameter 5-40 Function Relay [32] Mechanical
Brake Control
).
12
13 18
37
32
27
19
29
33 20
+24 V
P 5-10 [8]
P 5-12 [2]
P 5-02 [1]
P 5-31 [27]
GND
P 5-40 [0] [32]
Rela
y 1
01 02 03
-
+
130BA194.11
External
24 V DC
Mechanical brake
connection
Start
I
max
0.1 Amp
Illustration 12.8 Wire Configuration for Torque and Stop Limit
Application Examples
Design Guide
MG38C202
Danfoss A/S © 01/2018 All rights reserved.
191