130BB805.12
Speed
Start/Stop (18)
Illustration 12.2 Start/Stop with Safe Torque Off
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB803.10
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
[9] Latched
Start
Parameter 5-12 T
erminal 27
Digital Input
[6] Stop
Inverse
*=Default value
Notes/comments:
If
parameter 5-12 Terminal 27
Digital Input
is set to
[0] No
operation
, a jumper wire to
terminal 27 is not needed.
Table 12.6 Wiring Configuration for Pulse Start/Stop
Speed
130BB806.10
Latched Start (18)
Stop Inverse (27)
Illustration 12.3 Latched Start/Stop Inverse
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
130BB934.11
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
[8] Start
Parameter 5-11 T
erminal 19
Digital Input
[10]
Reversing*
Parameter 5-12 T
erminal 27
Digital Input
[0] No
operation
Parameter 5-14 T
erminal 32
Digital Input
[16] Preset ref
bit 0
Parameter 5-15 T
erminal 33
Digital Input
[17] Preset ref
bit 1
Parameter 3-10 P
reset Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
25%
50%
75%
100%
*=Default value
Notes/comments:
Table 12.7 Wiring Configuration for Start/Stop with Reversing
and 4 Preset Speeds
Application Examples
VLT® AutomationDrive FC 302
186
Danfoss A/S © 01/2018 All rights reserved.
MG38C202