VLT
®
AutomationDrive FC 302
N355
N400
N500
High/normal overload
HO
NO
HO
NO
HO
NO
(High overload=150% current during 60 s,
normal overload=110% current during 60 s)
Typical shaft output at 525 V [kW]
315
355
355
400
400
450
Typical shaft output at 575 V [hp]
400
450
400
500
500
600
Typical shaft output at 690 V [kW]
355
450
400
500
500
560
Enclosure size
E1h/E3h
E1h/E3h
E1h/E3h
Output current (3-phase)
Continuous (at 525 V) [A]
395
470
429
523
523
596
Intermittent (60 s overload) (at 525 V) [A]
593
517
644
575
785
656
Continuous (at 575/690 V) [A]
380
450
410
500
500
570
Intermittent (60 s overload) (at 575/690 V) [A]
570
495
615
550
750
627
Continuous kVA (at 525 V) [kVA]
376
448
409
498
498
568
Continuous kVA (at 575 V) [kVA]
378
448
408
498
498
568
Continuous kVA (at 690 V) [kVA]
454
538
490
598
598
681
Maximum input current
Continuous (at 525 V) [A]
381
453
413
504
504
574
Continuous (at 575/690 V) [A]
366
434
395
482
482
549
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
2
(AWG)]
5x240 (5x500 mcm)
5x240 (5x500 mcm)
5x240 (5x500 mcm)
- Mains and motor with brake [mm
2
(AWG)]
4x240 (4x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
- Brake or regen [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
Maximum number and size of cables per phase (E3h)
- Mains and motor [mm
2
(AWG)]
6x240 (6x500 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
- Brake [mm
2
(AWG)]
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
- Load share or regen [mm
2
(AWG)]
4x185 (4x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
Maximum external mains fuses [A]
1)
800
800
800
Estimated power loss at 600 V [W]
2), 3)
4989
6062
5419
6879
6833
8076
Estimated power loss at 690 V [W]
2), 3)
4920
5939
5332
6715
6678
7852
Efficiency
3)
0.98
0.98
0.98
Output frequency [Hz]
0–500
0–500
0–500
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [
°
C (
°
F)]
80 (176)
80 (176)
80 (176)
Power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
Fan power card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
Active in-rush card overtemperature trip [
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
Table 7.7 Electrical Data for Enclosures E1h/E3h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
Specifications
VLT® AutomationDrive FC 302
42
Danfoss A/S © 01/2018 All rights reserved.
MG38C202